INSTALLING THE UPS SYSTEM
Eaton
®
9390 UPS (20–80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual
S
164201603 Rev 4
www.eaton.com/powerquality
4-17
Installation Checklist
-
All packing materials and restraints have been removed from each cabinet.
-
Each cabinet in the UPS system is placed in its installed location.
-
Floor mounting brackets are installed and adjusted.
-
A cabinet grounding/mounting kit is installed between any cabinets that are bolted together.
-
All conduits and cables are properly routed to the UPS and any ancillary cabinets.
-
All power cables are properly sized and terminated.
-
Neutral conductors are installed or bonded to ground as per requirements.
-
Battery cables are terminated on E4 (+) and E5 (-). (Not applicable to the 9390IT internal batteriy configuraation).
-
Battery UV trip and Aux contact signal wiring is connected from the UPS to the battery breaker.
(Not applicable to the 9390IT internal battery configuration.)
-
LAN and telephone drops are installed.
-
All telephone and LAN connections have been completed.
-
A ground conductor is properly installed.
-
Air conditioning equipment is installed and operating correctly.
-
The area around the installed UPS system is clean and dust‐free. (Eaton recommends that the UPS be installed on a
level floor suitable for computer or electronic equipment.)
-
Adequate workspace exists around the UPS and other cabinets.
-
Adequate lighting is provided around all UPS equipment.
-
A 120 Vac service outlet is located within 7.5 meters (25 feet) of the UPS equipment.
-
The REPO device is mounted in its installed location and its wiring is terminated inside the UPS cabinet. The REPO
switch must be a latching‐type switch with a dedicated circuit.
-
The normally-closed (NC) Emergency Power-off contact (pins 1 and 2 on TB1) is jumpered if not used.
-
Alarm relays and building alarms are wired appropriately. (OPTIONAL)
-
A remote battery disconnect control is mounted in its installed location and its wiring is terminated inside the UPS and
battery cabinet. (OPTIONAL) (Not applicable to the 9390IT internal battery configuration)
-
Accessories are mounted in installed locations and wiring is terminated inside the UPS cabinet. (OPTIONAL)
-
The debris shield covering the UPS cabinet ventilation grill is removed.
-
Startup and operational checks are performed by an authorized Eaton Customer Service Engineer.