3 of 23
POWER WIRING INSTALLATION NOTES
071608
C
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
INSTALLATION INFORMATION
Eaton
®
9390 UPS (20–80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual
S
164201603 Rev 4
www.eaton.com/powerquality
A-15
Table H. Input/Output Ratings & External Wiring Requirements for the Powerware 9390/9390IT-40/40
and 9390-80/40
Units
Rating 50/60 Hz
Basic Unit Rating at 0.9 lagging pF
load
kVA
kW
40
36
40
36
40
36
40
36
40
36
Input and Bypass Input
Output
VOLTS
VOLTS
208/220
208/220
380
380
400
400
415
415
480
480
AC Input to UPS Rectifier
(0.98 min. pF)
Full Load Current plus Battery
Recharge Current
(3) Phases, (1) Ground
A
Amps
125
68
64
63
55
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
2/0
(1)
2
(1)
2
(1)
2
(1)
4
(1)
AC Input to UPS Bypass
Full Load Current
(3) Phases, (1) Neutral-if required,
(1) Ground
B
Amps
111/105
61
58
56
48
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
2/0
(1)
2
(1)
2
(1)
2
(1)
4
(1)
DC Input from Battery to UPS
(1) Positive, (1) Negative
C
Vdc
Amps@
(2.0V/cell)
384-480
101
432-480
101
432-480
101
432-480
101
432-480
101
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
1/0
(1)
1/0
(1)
1/0
(1)
1/0
(1)
1/0
(1)
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral-if required, (1)
Ground
D
Amps
111/105
61
58
56
48
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
2/0
(1)
2
(1)
2
(1)
2
(1)
4
(1)
Neutral Bonding Jumper
Minimum Conductor Size
Number (See Note 7)
-
AWG or kcmil
(each)
4
(1)
6
(1)
6
(1)
6
(1)
6
(1)
NOTE
Callout letters
A
,
B
,
C
, and
D
map to Drawing 164201603-5, sheets 1 of 6,
C
A
U
T
I
O
N
DELTA SOURCES (TN‐S) - The Eaton 9390 UPS system can be operated only from a delta supply source that is fully floating
and if the neutral‐forming transformer kit (PN 103005400) is installed in the UPS. The UPS cannot be operated from a
mid‐point or end‐point grounded delta supply source. With this type of supply source, there is no capability to provide an
output neutral. In no circumstances shall a neutral to ground bonding jumper be installed in the UPS.
8.
The UPS cabinet is shipped with a debris shield covering the ventilation grill on top of the
cabinet. Do not remove the debris shield until installation is complete. However, remove
the shield before operating the UPS. Once the debris shield is removed, do not place
objects on the ventilation grill.
9.
Refer to Section
I
of this manual for installation instructions.
Summary of Contents for 9390IT
Page 2: ......
Page 6: ...This page intentionally left blank...
Page 237: ......
Page 238: ...1642016034 164201603 4...