UPS SYSTEM INSTALLATION
Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual
S
164201710 Rev 2
www.eaton.com\powerquality
4-9
10.
If wiring a distributed bypass system, proceed to Step 11; otherwise, proceed to
Step 13.
C
A
U
T
I
O
N
Distributed bypass system wiring length should be in accordance with Figure 4‐5, to ensure approximately
equal current sharing when in Bypass mode.
11.
Using hardware from the external wiring terminal hardware kit (see Table 3‐8 on
page 3-12), connect phase A, B, and C, and Neutral power wiring from the output
and neutral terminals of each UPS unit to the customer-supplied tie cabinet or
load distribution panel. See paragraph 3.2.2 on page 3-6 for wiring and
termination requirements.
12.
Proceed to paragraph 4.5.3.
13.
Using hardware from the external wiring terminal hardware kit (see Table 3‐8 on
page 3-12), connect phase A, B, and C, and Neutral (if required) power wiring
from output terminals and neutral terminals to the critical load. See
paragraph 3.2.2 on page 3-6 for wiring and termination requirements.
14.
Proceed to paragraph 4.5.3.