INSTALLING OPTIONS AND ACCESSORIES
Eaton 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual
S
164201710 Rev 2
www.eaton.com\powerquality
5-6
1
2
3
4
5
7
8
6
9
10
UPS 1
Twisted Pair
Twisted Pair
Twisted Pair
Twisted Pair
Twisted Pair
Twisted Pair
1
2
3
4
5
7
8
6
9
10
1
2
3
4
5
7
8
6
9
10
UPS 2
1
2
3
4
5
7
8
6
9
10
1
2
3
4
5
7
8
6
9
10
UPS 3
(If Installed)
1
2
3
4
5
7
8
6
9
10
1
2
3
4
5
7
8
6
9
10
1
2
3
4
5
7
8
6
9
10
Twisted Pair
UPS 4
(If Installed)
TB1
TB1
TB1
TB1
TB2
TB2
TB2
TB2
NOTE
Use twisted-pair wiring between the UPS and MOB AUX contacts.
Figure 5‐5. Distributed Bypass Pull-Chain Wiring without MOBs
Table 5‐3. Pull-Chain Wiring Terminations
From
UPS 1
To
UPS 2
To
UPS 3
(If Installed)
To
UPS 4
(If Installed)
TB2–1
(Pull Chain)
TB2–1
(Pull Chain)
TB2–1
(Pull Chain)
TB2–1
(Pull Chain)
TB2–2
(Pull Chain Common)
TB2–2
(Pull Chain Common)
TB2–2
(Pull Chain Common)
TB2–2
(Pull Chain Common)