UPS INSTALLATION PLAN AND UNPACKING
EATON
Powerware
®
9395 UPS (1000–1100 kVA) Installation and Operation Manual
S
164201764 Rev 1
www.powerware.com
3−14
Terminals E1 through E12 are 2-hole busbar mountings for standard NEMA 2-hole
barrel lugs. The power wiring connections for this equipment are rated at 90
°
C. See
Table 3-10 for power cable terminations, Table 3-11 for supplied terminal hardware,
and Table 3-12 for recommended installation parts and tools not supplied by Eaton
Corporation.
Figure 4-18 on page 4−21 and Figure 4-19 on page 4−22 show the location of the
power cable terminals inside the UPS.
Table 3-10. UPS External Power Cable Terminations for the Four UPM Powerware 9395−1100/1000 and 9395−1100/1100, and the Three UPM
Powerware 9395−1100/650, 9395−1100/750, and 9395−1100/825
Terminal Function
Terminal
Function
Bus Landings
(using both sides of bus)
Tightening Torque
Nm (lb ft)
Bolt Size
AC Input to UPS Rectifier
E1
Phase A
6 – 2 bolt mounting
76 (56)
M12
E2
Phase B
6 – 2 bolt mounting
76 (56)
M12
E3
Phase C
6 – 2 bolt mounting
76 (56)
M12
AC Input to Bypass
E6
Phase A
6 – 2 bolt mounting
76 (56)
M12
E7
Phase B
6 – 2 bolt mounting
76 (56)
M12
E8
Phase C
6 – 2 bolt mounting
76 (56)
M12
AC Output to Critical Load
E9
Phase A
6 – 2 bolt mounting
76 (56)
M12
E10
Phase B
6 – 2 bolt mounting
76 (56)
M12
E11
Phase C
6 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or Battery
Disconnect to UPS – Common
Battery
E4
Battery (+)
16 – 2 bolt mounting
76 (56)
M12
E5
Battery (−)
16 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or Battery
Disconnect to UPS – Separate
Battery (UPM 1)
E4
Battery (+)
4 – 2 bolt mounting
76 (56)
M12
E5
Battery (−)
4 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or Battery
Disconnect to UPS – Separate
Battery (UPM 2)
E4
Battery (+)
4 – 2 bolt mounting
76 (56)
M12
E5
Battery (−)
4 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or Battery
Disconnect to UPS – Separate
Battery (UPM 3)
E4
Battery (+)
4 – 2 bolt mounting
76 (56)
M12
E5
Battery (−)
4 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or Battery
Disconnect to UPS – Separate
Battery (UPM 4 FI−UPM)
E4
Battery (+)
4 – 2 bolt mounting
76 (56)
M12
E5
Battery (−)
4 – 2 bolt mounting
76 (56)
M12
Input and Output Neutral
E12
Neutral
12 – 2 bolt mounting
22 (16)
M10
Customer Ground
Ground
Ground
15 – 1 bolt mounting
22 (16)
M10
NOTE
Customer ground, sized in accordance with NEC Table 250.122, can be run in any conduit listed in Table 3-13 on page 3−16.