7.3.10
Using the UPS LOAD OFF Pushbutton or Command
A UPS Load Off is initiated by the
LOAD OFF
pushbutton from the main menu bar, the
Load Off command on the UPS Control Command screen, or Load Off command on
the Bypass Control Command screen. The UPS
LOAD OFF
controls the UPS output by
powering down the UPS and de-energizing the critical load.
The UPS (including Bypass) remains off until restarted.
To use the
LOAD OFF
pushbutton:
1.
Press the
LOAD OFF
pushbutton.
The Load Off screen is displayed, providing a choice to proceed or abort the
shutdown.
C
A
U
T
I
O
N
All power to the critical load is lost when the LOAD OFF is selected in the following step. You should use this
feature only when you want to de-energize the critical load.
2.
To shut down the UPS, press
LOAD OFF
from the Load Off menu bar, and hold for
three seconds. To abort the shutdown, press
CANCEL
.
When LOAD OFF is selected and held for three seconds, the input, output,
battery, and bypass backfeed contactors open, and the power module is turned
off.
C
A
U
T
I
O
N
Do not attempt to restart the system after Load Off until the cause of the shutdown has been identified and
cleared.
3.
To restart the UPS after pressing the
LOAD OFF
pushbutton, follow the procedure
in paragraph 7.3.1 on page 7−11 or 7.3.2 on page 7−12.
W
A
R
N
I
N
G
Power is present inside the UPS cabinet sections until the upstream input feeder circuit breaker is opened.
To use the
LOAD OFF
command:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status
screen is displayed.
2.
On the System Status screen, select either the
UPS
or the
BYPASS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The UPS or
Bypass Control Command screen is displayed.
4.
On the Control Command screen, select
LOAD OFF
.
5.
Press the
SELECT
pushbutton on the Command menu bar.
The Load Off screen is displayed, providing a choice to proceed or abort the