Product Specifications
10-2
Eaton
®
Power Xpert
®
9395C UPS Installation and Operation Manual
P-164000821—Rev 01
www.eaton.com/powerquality
10.2.2 UPS Output
10.2.3 UPS Environmental
10.2.4 Battery RunTime Ratings
UPS Output Capacity
100% rated current
Output Voltage Regulation
±1.5% (10% to 100% load)
Output Voltage
(N/–3%)
480 Vac nominal, adjustable from 466 Vac to 494 Vac
Output Voltage Harmonic Content
1% maximum THD (linear load)
5% maximum THD (nonlinear load)
Output Current
Output Voltage Balance
2.5% for 100% maximum load imbalance (linear load)
Output Voltage Phase
Displacement
±4° for 100% maximum load imbalance (linear load)
Output Transients
Meets Class 1 IEC 62040-3 (10% to 100% load)
Frequency Regulation
±0.1 Hz free running
Synchronous to Bypass
+10% to -10%
Frequency Slew Rate
.7 Hz per second maximum
Load Compatibility
0.9 pF Leading
0.7 pF Lagging
Overload Capability (kVA or kW)
110% for 10 minutes
125% for 120 seconds
150% for 15 seconds
NOTE
The 125% and 150% overloads are based on the non-derated hardware capability of the UPS.
Operating Temperature
0 to 40°C (32 to 104°F) at elevation up to 1000m without derating.
The recommended operating temperature is 25°C (77°F).
Operating Altitude
Maximum 1000 m (3300 ft) at 40°C without derating
Storage Temperature
–25 to +60°C excluding batteries (prolonged storage above 40°C causes
rapid battery self-discharge)
Relative Humidity (operating and storage)
5% to 95% maximum noncondensing
Agency Markings
78 dB at a 1m distance, A weighted for one UPS
EMI Emissions and Immunity
Meets IEC 62040-2, category C3
Electrostatic Discharge (ESD) Immunity
Meets IEC 801-2 specifications. Withstands up to 25 kV pulse without
damage and with no disturbance or adverse effect to the critical load.
kVA
kW
Ambient
Temperature
Battery
Runtime
(minutes)
1100
1100
35°C (95°F)
12
1100
1000
40°C (104°F)
20
1000
1000
40°C (104°F)
20
NOTE
Timer will be disabled below 700kW