Installation Plan and Unpacking
3-2
Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2
www.eaton.com/powerquality
The IAC-D cabinet uses convection cooling to regulate internal component temperature. Air inlets are in the
front of the cabinet and outlets are in the back of the cabinet. Allow clearance in front of and in back of the
cabinet for proper air circulation. The clearances required around the IAC-D cabinet are shown in Table 3-2.
The basic environmental requirements for operation of the IAC-D are:
- Recommended Operating Range: 15–25
C (59–77
F)
- Maximum Relative Humidity: 95%, noncondensing
Table 3-1. IAC-D Cabinet Weights
Model
Weight
kg (lb)
Shipping
Installed
Point Loading
Eaton 93E 30IAC-D
133 (293)
108 (238)
6 at 18 (39.7)
Eaton 93E 60IAC-D
168 (370)
143 (315)
6 at 23.9 (52.5)
Table 3-2. IAC-D Cabinet Clearances
From Top of Cabinet
None Required
From Front of Cabinet
914.4 mm (36") working space
From Back of Cabinet
914.4 mm (36") working space
From Right Side of Cabinet
None Required
From Left Side of Cabinet
None Required