Item
Value
Maximum rate of temperature change**
1.67 °C/ 5 min
*Note: For a maximum lifetime for the UPS and batteries, keep the environment
in the recommended range.
**Note: The limit is based on ASHRAE 90.1-2013. Rapidly increasing
temperature can cause condensation on colder surfaces.
9.5 Directives and standards
Safety
IEC 62040-1: Uninterruptible power systems (UPS) - Part
1: General and safety requirements for UPS
IEC 62447-1: Information technology equipment - Safety -
Part 1: General requirements (as referred through the IEC
62040-1)
EMC
IEC 62040-2: Uninterruptible power systems (UPS) - Part
2: Electromagnetic compatibility (EMC) requirements / Ed.
3
•
Emissions: category C3
•
Immunity: category C3
Environmental
IEC62040-4: Uninterruptible Power Systems (UPS) - Part
4: Environmental Aspects - Requirements and Reporting
IEC 62430: Environmentally conscious design for electrical
and electronic products
RoHS
2011/65/EU on the restriction of the use of certain hazard-
ous substances in electrical and electronic equipment
WEEE
2012/19/EU on waste electrical and electronic equipment
(WEEE)
Batteries
2006/66/EC on batteries and accumulators and waste bat-
teries and accumulators
Packaging
94/62/EC on packaging and packaging waste
Eaton 93E Generation 2 UPS 100-200 kVA
(380/400/415V)
User's and installation guide
©
Eaton Corporation plc 2019. All rights reserved.
Revision: 002
Document ID: P-164000848