5 UPS system installation
The operator has to supply the wiring to connect the UPS to the local power
source. The installation of the UPS must be made by a locally qualified
electrician. The electrical installation procedure is described in the following
section. The installation inspection and the initial start-up of the UPS and
installing an external battery cabinet must be carried out by an authorized Eaton
Field Service Engineer or by other qualified service personnel authorized by
Eaton.
CAUTION
To avoid physical injury or death, or damage to the UPS or the load
equipment, follow these instructions during the UPS system installation.
WARNING
Only qualified personnel are allowed to perform the installation. See the
installation instructions before connecting to the supply.
Refer to the following while installing the UPS system:
• Chapter
for cabinet dimensions, equipment weight, cabling and terminal
data, and installation notes.
• Do not tilt the cabinets more than ±10° during the installation.
• If perforated floor tiles are required for ventilation, place them in front of the
UPS.
• The UPS unit is not suitable for IT, TT or corner-earthed power distribution
systems.
• Suitable for mounting on concrete or other non-combustible surfaces only.
5.1 Installing UPS external battery cabinet and battery
power cabling
For 93E 100-200 kVA UPS, in stored energy mode, the power is provided by
external batteries. The UPS can be equipped with up to four External Battery
Cabinets (EBCs) containing sealed lead-acid, maintenance-free batteries. A
single EBC can contain 36, 38 or 40 batteries. Power and control wiring are not
supplied with the UPS.
When installing Eaton External Battery Cabinets (EBCs), refer to the
manufacturer’s installation manual for installation instructions.
If installing a customer-supplied battery system, install the battery system
according to the battery and battery system manufacturer’s instructions and all
applicable codes and regulations.
Eaton 93E Generation 2 UPS 100-200 kVA
(380/400/415V)
User's and installation guide
©
Eaton Corporation plc 2019. All rights reserved.
Revision: 002
Document ID: P-164000848
55 (118)