remote EPO switch for this function. Make sure that the wiring of the
remote EPO switch is in accordance with local regulations.
Table 17: Normally-open remote EPO wire connections
From remote EPO
station(s) switch
contact block
(either contact)
To remote EPO
terminal block
on the back of UPS
cabinet
Wire size
Tightening torque
3 N.O. 3
for
wiring
Twisted wires (2)
(0.5 -2.0 mm
2
)
0.8 Nm
4 N.O. 4
Figure 29. Normally-open remote EPO switch wiring
A Remote EPO switch (N.O.)
C
UPS Remote EPO terminal (REPO)
B Twisted wires
Table 18: Normally-closed remote EPO wire connections
From remote EPO
station(s) switch
contact block
(either contact)
To remote EPO
terminal block
on the back of UPS
cabinet
Wire size
Tightening torque
1 N.C. 1
for
wiring
Twisted wires (2)
(0.5 -2.0 mm
2
)
0.8 Nm
2 N.C. 2
Eaton 93E Generation 2 UPS 100-200 kVA
(380/400/415V)
User's and installation guide
©
Eaton Corporation plc 2019. All rights reserved.
Revision: 002
Document ID: P-164000848
70 (118)