Figure 39. Typical system control screen
Table 22: Command menu operation
Function
Sub-func-
tion
Operation
UPS Con-
trol Com-
mands
Use the or push button to highlight the desired com-
mand function, then press the
push button to execute the
command or proceed to further command screens.
Normal
Mode
Starts the UPS in the double conversion (normal) mode, or
transfers the UPS from the bypass mode to the double conver-
sion (normal) mode.
Bypass
Mode
Starts the UPS in the bypass mode, or transfers the UPS to
the bypass mode from double conversion, stored energy or HE
modes.
High-Effi-
ciency
(HE) Mode
Transfers the UPS from the double conversion (normal) mode
to the HE mode. Transfers the UPS from the HE mode to the
double conversion (normal) mode. Transfer to the HE mode
will not happen instantly. Charging current needs to be at an
appropriate level so that the HE mode can be supported.
Load off
When the unit is in the double conversion mode, the load off
command turns off the inverter, but the rectifier and charger
will stay on. In the bypass mode, the load off command turns
off the SCRs and stops the load supply.
Battery
Control
Com-
mands
Use the or push button to highlight the desired com-
mand function, then press the
push button to execute the
command.
Charger
Turns the battery charger on.
Resting
Turns the battery charger off.
Testing
When the charger is turned off, the testing command is availa-
ble for performing battery capacity testing.