9 Technical data
For a complete technical specification, contact your Eaton representative. Due
to continuous product improvement programs, specifications are subject to
change without notice.
9.1 Model numbers
The UPS is housed in a free-standing cabinet with safety shields behind the
door. The UPS is available in 50 or 60 Hz with various output power ratings.
Table 23: Model numbers
Models
Power rating
Frequency
Eaton 93E G2 100/100
100 kVA
50/60 Hz
Eaton 93E G2 120/120
120 kVA
50/60 Hz
Eaton 93E G2 200/160
160 kVA
50/60 Hz
Eaton 93E G2 200/200
200 kVA
50/60 Hz
9.2 UPS system input
Table 24: UPS input
Item
Value
Number of input phases (rectifier & bypass) 3 N
Operating input voltage
380/400/415 Vac
Input voltage range
196/330–276/478V at 100% load
126/201-276/478V at 50% load
Operating input frequency range
50/60 Hz
Input frequency range
40-72 Hz
Operating input current
Input current distortion, iTHD
< 3% at load range 80% to 100%
Power factor
> 0.99 at rated load
Back feed protection
Yes, for rectifier and bypass lines
Line surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC
801 4
Table 25: Battery specification
Item
Value
Battery voltage
432 VDC (36 blocks), 456 VDC (38 blocks)
or 480 VDC (40 blocks)
Eaton 93E Generation 2 UPS 100-200 kVA
(380/400/415V)
User's and installation guide
©
Eaton Corporation plc 2019. All rights reserved.
Revision: 002
Document ID: P-164000848
107 (118)