Item
Value
Load power factor (rated)
nominal 0.9
Overload capability in double conversion
(normal) mode
≤ 125% for 10 minutes
≤ 150% for 1 minute
≥ 150% for 500 milliseconds
Overload capability in the stored energy
mode
102 - 125% for 1 minute
126 - 150% for 30 seconds
> 150% for 150 milliseconds
Overload capability in the bypass mode
< 115% continuous of nominal line current
Transient 10 x peak current for 20 millisec-
onds
Output current limitation, short circuit capa-
bility (rms)
100 kVA UPS: 350 A
120 kVA UPS: 440 A
160 kVA UPS: 720 A
200 kVA UPS: 720 A
9.4 UPS environmental specifications
Table 27: UPS environmental specifications
Item
Value
Operating temperature
0 to 40 °C without derating. The recom-
mended operating temperature is 20 to 25
°C.
Operating altitude
1000 m without derating, up to 2000 m with
derating
Storage temperature
- 25 to 55 °C, excluding batteries (pro-
longed storage above 40 °C causes rapid
battery selfdischarge)
Relative humidity (operating and storage)
5% to 95% maximum noncondensing, rec-
ommended range* 20% to 60%
Pollution degree
min PD2
Protective class
Protective class I
IP class
IP20
Earthing systems
TN-s, TN-C, or TN-C-S
Electrical (overvoltage category)
OVCIII
Acoustical noise
≤ 62 dB (100-120kVA) and 70 dB (160-200
kVA) at a 1 m distance, at 75% load, per
ISO 7779
EMC
IEC 62040-2 ed.3 C3
Eaton 93E Generation 2 UPS 100-200 kVA
(380/400/415V)
User's and installation guide
©
Eaton Corporation plc 2019. All rights reserved.
Revision: 002
Document ID: P-164000848
109 (118)