Table 10: UPS external power cable terminations for the Eaton 93E 160-200 kVA
Terminal function Termi-
nal
Func-
tion
Bus landing
Tighten-
ing tor-
que Nm
(lb in)
Bolt size and type
AC input to UPS
rectifier
L1
Phase
A
M10 bolt mount-
ing
14
(124)
78.540 mm
2
(M10
Hex bolt)
L2
Phase
B
M10 bolt mount-
ing
14
(124)
78.540 mm
2
(M10
Hex bolt)
L3
Phase
C
M10 bolt mount-
ing
14
(124)
78.540 mm
2
(M10
Hex bolt)
N
Neutral M10 bolt mount-
ing
14
(124)
78.540 mm
2
(M10
Hex bolt)
AC input to by-
pass
L1
Phase
A
M10 bolt mount-
ing
14
(124)
78.540 mm
2
(M10
Hex bolt)
L2
Phase
B
M10 bolt mount-
ing
14
(124)
78.540 mm
2
(M10
Hex bolt)
L3
Phase
C
M10 bolt mount-
ing
14
(124)
78.540 mm
2
(M10
Hex bolt)
N
Neutral M10 bolt mount-
ing
14
(124)
78.540 mm
2
(M10
Hex bolt)
AC output to criti-
cal load
L1
Phase
A
M10 bolt mount-
ing
14
(124)
78.540 mm
2
(M10
Hex bolt)
L2
Phase
B
M10 bolt mount-
ing
14
(124)
78.540 mm
2
(M10
Hex bolt)
L3
Phase
C
M10 bolt mount-
ing
14
(124)
78.540 mm
2
(M10
Hex bolt)
N
Neutral M10 bolt mount-
ing
14
(124)
78.540 mm
2
(M10
Hex bolt)
DC input from ex-
ternal battery
+
Battery
(+)
M10 bolt mount-
ing
14
(124)
78.540 mm
2
(M10
Hex bolt)
–
Battery
(–)
M10 bolt mount-
ing
14
(124)
78.540 mm
2
(M10
Hex bolt)
Customer ground Ground Ground M10 bolt mount-
ing
14
(124)
78.540 mm
2
(M10
Hex bolt)
See also Figure
Table 11: Input/Output ratings and external wiring recommendations for the Eaton 93E
100-200 kVA
Units
Rating 50/60 Hz
Basic unit rating
Cross
sections
kVA
100
120
160
200
kW
90
108
144
180
Eaton 93E Generation 2 UPS 100-200 kVA
(380/400/415V)
User's and installation guide
©
Eaton Corporation plc 2019. All rights reserved.
Revision: 002
Document ID: P-164000848
44 (118)