Table 13: Recommended external fuse ratings for Rated conditional short-circuit current
(Icc) of 65 kA
Rated power
Rectifier input /Bypass/MBS (Icc:
65 kA)
Battery (Icc: 22 kA)
100 kVA
170M3420, 170M3470,
170M3520, 150M3570 (450 A/
690 V)
170M3418, 170M3468,
170M3518, 150M3568 (350 A/
690 V)
120 kVA
170M3422, 170M3472,
170M3522, 150M3572 (550 A/
690 V)
170M3420, 170M3470,
170M3520, 150M3570 (450 A/
700 V)
160 kVA
170M4417, 170M4467,
170M4517, 150M4567 (700 A/
690 V)
170M4417, 170M4467,
170M4517, 150M4567 (700 A/
690 V)
200 kVA
170M4417, 170M4467,
170M4517, 150M4567 (700 A/
690 V)
170M4417, 170M4467,
170M4517, 150M4567 (700 A/
690 V)
The battery wiring used between the battery and the UPS should not allow a
voltage drop of more than 1% of nominal DC voltage at rated battery current.
4.3.3
UPS system interface wiring preparation
Control wiring for features and options should be connected at the customer
interface terminal blocks located inside the UPS.
WARNING
Do not directly connect contactor contacts to the mains related circuits.
Reinforced insulation is required before connecting to the mains.
Read and understand the following notes while planning and performing the
installation:
• Interface wiring should be rated for 24V, 1A minimum.
• For interface wiring from 30V to 600V, the wire should be rated for 600V, 1A
minimum.
• Because of the remote EPO and signal input wiring route in the UPS
cabinet, the wire should be rated for a minimum of 300V.
• Use twisted-pair wires for each input and return or common.
• All interface wiring and conduit is to be supplied by the customer.
• When installing external interface wiring between a remote EPO or signal
input and the UPS interface terminals, conduit must be installed between
each device and the UPS cabinet.
• If using the power terminal wiring channel, keep interface wiring separate
from power wiring or use shielded wire.
• Interface wiring circuits are PELV circuits.