Figure 21. Blocking the space between the cable and cabinet
1
Space to be blocked with fireproof mud
5.3 Installing interface connections
5.3.1
Installing signal input connections
To install wiring:
1.
Make sure that the UPS system is turned off and all power sources are
removed. See Chapter
for shutdown instructions.
2.
To locate the appropriate terminals and review the cabling and termination
requirements, see Section
, Figure
3.
Route the interface cables to the UPS via the right side panel or the
knockout at the top (front right corner) of the cabinet.
4.
Connect the signal input interface cabling as shown in Table
and Figure
5.
If you are cabling parallel connections, proceed to Section
cabling MiniSlot connections, proceed to Section
.
Eaton 93E Generation 2 UPS 100-200 kVA
(380/400/415V)
User's and installation guide
©
Eaton Corporation plc 2019. All rights reserved.
Revision: 002
Document ID: P-164000848
62 (118)