Note: The maintenance bypass operation must be performed by an Eaton
authorized Customer Service Engineer.
WARNING
Power is present inside the UPS cabinet.
Figure 40. 100-120 kVA Optional internal maintenance bypass switch arrangement
1
Output switch
4
Input switch
2
Maintenance bypass switch
5
Neutral switch
3
Bypass input switch
7.3.8
Transferring from internal maintenance bypass to normal mode
(optional on 100-120 kVA)
To transfer the load to the normal mode, perform the following procedure:
1.
Close the neutral switch, slide the cover plate right, and tighten the screws.
2.
Close the input and bypass input switches.
3.
Restart the UPS in bypass mode by performing the procedure in Section
.
4.
Verify that the UPS is in the bypass mode.
5.
Close the output switch.
6.
Open the maintenance bypass switch (MBS), slide the cover plate left, and
tighten the screws.
7.
Transfer the load to the double conversion (normal) mode. For instructions,
or
7.3.9
Shutting down the UPS system and critical load
To perform maintenance or service on the critical load, shut down the power to
the load by performing the following procedure: