UPS Installation Plan and Unpacking
Eaton 93E UPS (300/400 kVA, 380/400/415V) Installation and Operation Manual
3-7
CAUTION
External overcurrent protection is not provided by this product, but is required by codes. Refer to
table 3-5 for wiring requirements. If an input/output lockable disconnect is required, it is to be
supplied by the user.
Basic Unit Rating
cross-sections
Units
Rating 50/60 Hz
kVA
kW
300
270
400
360
Input and Output Voltage
Volts
400/400
400/400
AC Input to UPS Rectifier (0.99 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Neutral, (1) Ground
Amps
460
613
Conductor Size (Phase A, B, C and N)
min
mm
2
150
240
max
mm
2
300
400
AC Input to UPS Bypass (Five Wire, Dual-Feed)
Full Load Current
(3) Phases, (1) Neutral
Amps
433
577
Conductor Size (Phase A, B, C )
min
mm
2
150
240
max
mm
2
300
400
Conductor Size (N)
min
mm
2
150
240
max
mm
2
300
400
DC Input from External Battery
(1) Positive, (1) Negative
Total Amps
618
824
Conductor Size
min
mm
2
240
370
max
mm
2
400
500
AC Output to Critical Load (Five Wire)
Full Load Current
(3) Phases, (1) Neutral
Amps
433
577
Conductor Size (Phase A, B,C )
min
mm
2
150
240
max
mm
2
300
400
Conductor Size (N)
min
mm
2
150
240
max
mm
2
300
400
Grounding
Amps
460
613
Conductor Size (Ground)
min
mm
2
150
240
max
mm
2
300
400
Neutral (N) (Mains/Load):( Non-linear load )
1.7times
Backfeed protection device
Clearance distance:> =2.0mm
Break time < =15s
NOTE
Callout letters
A
,
B
,
C
, and
D
map to Figure 5-5.
Table 3-5.Input/Output Ratings and External Wiring Requirements for the Eaton 93E 300/400kVA