background image

UPS Operating Instructions

 

                                                                                                                              Eaton 93E UPS (300/400 kVA, 380/400/415V) Installation and Operation Manual 

6-5

Figure 6-4.  Parts of the LCD

6.2.3    Using the LCD and Pushbuttons

The LCD on the control panel provides an operator interface with the UPS system. Figure 6-4 identifies the 
display areas discussed in the following sections.

The UPS status area automatically scrolls between the Eaton model number, current date and time, active 
alarms, UPS status, load percent, and battery runtime for the UPS. The top line of display blinks while 
scrolling when the system needs attention. Some notices and alarms may be accompanied by an audible 
horn. To silence the horn, press any control panel pushbutton once. Shown is a typical alarm message. For 
more information about alarms and notices, see paragraph 6.2.2.

The information area contains data about UPS status and operations.

The menu bar shows the symbols of the available screens. To select a screen, highlight the screen symbol 
using the navigation pushbuttons and then press the RETURN pushbutton.

The navigation pushbuttons function depending on the screen displayed. Use the Up, Down, Left, and 
Right pushbuttons to scroll through available screens and the Esc and Enter pushbuttons to select menu 
screens and functions.

You can use the LCD and the pushbuttons to:

• 

Look at a log of UPS events (alarms, notices, and commands) (see paragraph 6.2.6)

• 

Monitor UPS operation (see paragraph 6.2.6)

• 

Set UPS parameters (see paragraph 6.2.6)

• 

Control UPS operation (see paragraphs 6.2.6 and 6.2.7)

After approximately 10 minutes, the display screen darkens. To restore the screen, press any pushbutton once.

A

B

C

D

Alarm:

Alarm:

Alarm:

Alarm: Output

Output

Output

Output AC

AC

AC

AC Under

Under

Under

Under Voltage

Voltage

Voltage

Voltage

A

B

C

D

Meter

Events

History

Controls

Setup

Summary of Contents for 93E

Page 1: ...300 400 kVA 380 400 415V Installation and Operation Manual Eaton 93E UPS...

Page 2: ......

Page 3: ...ur Veuillez consulter enti rement ces instructions avant de faire fonctionner l quipement et conserver ce manuel afin de pouvoir vous y reporter ult rieurement Eaton Powerware and Mini Slot are regist...

Page 4: ......

Page 5: ...allation Plan and Unpacking 3 1 3 1 Creating an Installation Plan 3 1 3 2 Preparing the Site 3 1 3 2 1 Environmental and Installation Considerations 3 1 3 2 2 UPS System PowerWiring Preparation 3 5 3...

Page 6: ...ansfer from Normal to Bypass Mode 6 12 6 3 4 Transfer from Bypass to Normal Mode 6 13 6 3 5 Transfer from Standard Normal Mode to HE mode 6 13 6 3 6 Transfer from HE Mode to Standard Normal Mode 6 13...

Page 7: ...structions 8 1 8 2 Performing Preventative Maintenance 8 2 8 2 1 DAILY Maintenance 8 2 8 2 2 MONTHLY Maintenance 8 2 8 2 3 ANNUAL Maintenance 8 3 8 2 4 BATTERY Maintenance 8 3 8 3 Installing Batteries...

Page 8: ...Table of Contents iv Eaton 93E UPS 300 400 kVA 380 400 415V Installation and Operation Manual This page intentionally left blank...

Page 9: ...ions 4 10 Figure 4 7 REPOTerminal Block Connector Assignments 4 11 Figure 4 8 Normally Open REPO SwitchWiring 4 12 Figure 4 9 Normally Closed REPO SwitchWiring 4 13 Figure 5 1 Main Elements of the UPS...

Page 10: ...List of Figures vi Eaton 93E UPS 300 400 kVA 380 400 415V Installation and Operation Manual This page intentionally left blank...

Page 11: ...ons for the Eaton 93E 300 400kVA 3 8 Table 3 7 Recommended Input Circuit Breaker Ratings 3 8 Table 3 8 Recommended Bypass and Output Circuit Breaker Ratings 3 9 Table 3 9 Recommended DC input circuit...

Page 12: ...List of Tables viii Eaton 93E UPS 300 400 kVA 380 400 415V Installation and Operation Manual This page intentionally left blank...

Page 13: ...lectrical system the UPS system supplies clean consistent power that sensitive electronic equipment requires for reliable operation During brownouts blackouts and other power interruptions batteries p...

Page 14: ...rs a High Efficiency HE normal mode with double conversion on demand that allows the UPS to operate in standby bypass mode This mode allows the 93E UPS to achieve 98 efficiency while still protecting...

Page 15: ...manual to ensure trouble free installation and operation In particular be thoroughly familiar with the REPO procedure see paragraph 6 3 13 The information in this manual is divided into sections and c...

Page 16: ...ste centre This symbol indicates that you should not discard waste electrical or electronic equipment WEEE in the trash For proper disposal contact your local recycling reuse or hazardous waste centre...

Page 17: ...C 104 F Do not operate near water or excessive humidity 95 maximum The system is not intended for outdoor use As a result of the connected loads high leakage current is possible Connection to earth gr...

Page 18: ...and front panels installed to ensure proper cooling airflow and to protect personnel from dangerous voltages inside the unit Do not install or operate the UPS system close to gas or electric heat sour...

Page 19: ...Section 1 Installation...

Page 20: ......

Page 21: ...art of the sales contract for the UPS Contact an Eaton service representative in advance usually a two week notice is required to reserve a preferred startup date 3 2 Preparing the Site For the UPS sy...

Page 22: ...ic environmental requirements for operation of the UPS are AmbientTemperature Range 0 40 C 32 104 F Recommended Operating Range 20 25 C 68 77 F Maximum Relative Humidity 95 noncondensing Notes L1 clea...

Page 23: ...Installation and Operation Manual 3 3 Figure 3 1 UPS Cabinet Dimensions Front and Right Side Views Dimensions are in millimetres inches FrontView TopView BottomView RightView RearView Figure 3 2 UPS C...

Page 24: ...followed if they are more stringent than the UPS requirements Operating temperatures above the recommended range will result in decreased battery life and performance and may reduce or void the batter...

Page 25: ...VOLTAGE BETWEEN ALL TERMINALS INCLUDING THE PROTECTIVE EARTH RISK OF VOLTAGE BACKFEED UPS Refer to national and local electrical codes for acceptable external wiring practices To allow for future kVA...

Page 26: ...installation site near the UPS Install a proper three pole overcurrent disconnect device or four pole overcurrent disconnect device before connecting to the UPS the disconnect device shall disconnect...

Page 27: ...400 AC Input to UPS Bypass Five Wire Dual Feed Full Load Current 3 Phases 1 Neutral Amps 433 577 Conductor Size Phase A B C min mm2 150 240 max mm2 300 400 Conductor Size N min mm2 150 240 max mm2 30...

Page 28: ...M10 bolt mounting 47 416 78 5 mm2 M10 Hex AC Output to Critical Load L1 Phase A M10 bolt mounting 47 416 78 5 mm2 M10 Hex L2 Phase B M10 bolt mounting 47 416 78 5 mm2 M10 Hex L3 Phase C M10 bolt moun...

Page 29: ...PS A battery disconnect switch is recommended And may be required by local codes when batteries are remotely located The battery disconnect breaker should be installed between the battery and the UPS...

Page 30: ...erface terminals conduit must be installed between each device and the UPS cabinet If using the power terminal wiring channel keep interface wiring separate from power wiring or use shielded wire If u...

Page 31: ...entre of gravity measurements CAUTION Do not tilt the UPS cabinets more than 15 from vertical or the cabinets may tip over 3 Set the pallet on a firm level surface allowing a minimum clearance of 3m 1...

Page 32: ...UPS Installation Plan and Unpacking This page intentionally left blank 3 12 Eaton 93E UPS 300 400 kVA 380 400 415V Installation and Operation Manual...

Page 33: ...r bolts securing the bracket to the pallet see Figure 4 1 Remove the shipping bracket If installing the cabinet permanently retain the shipping bracket and securing hardware for later use 3 Roll the c...

Page 34: ...ping Bracket Bolts 4 3 External Maintenance Bypass Installation The Maintenance Bypass for 300 400 kVA models consists of input output and bypass breakers used to control the AC input to the UPS the i...

Page 35: ...bles sized according to cable cross section and protective device specification to terminals positive pole and negative pole e Refer to instructions provided with the battery cabinet or by vendor CAUT...

Page 36: ...input N and Bypass input N are connected together inside UPS For single feed installation jumpers the input and bypass terminals L1 L1 L2 L2 L3 L3 must be installed For a detailed view of the UPS term...

Page 37: ...itical Load AC Output to Critical Load Phase A Ll Phase B L2 Phase C L3 Phase A Ll Phase B L2 Phase C L3 Phase A Ll Phase B L2 Phase C L3 Contain Breaker and Backfeed Contactor Contain no Breaker and...

Page 38: ...ng Instructions for shutdown instructions 2 To locate the appropriate terminals and review the wiring and termination requirements see paragraph 3 2 3 Table 4 1 Figure 4 2and Figure 4 3 Figure 4 3 Int...

Page 39: ...remote dry contact closure 2 Building Alarm 1 3 Building Alarm 2 Input Programmable UPS alarm activated by a remote dry contact closure 4 Building Alarm 2 5 Building Alarm 3 Input Programmable UPS ala...

Page 40: ...1 and connected hole 2 that are use for parallel cables routing 6 Route and install pull chain wiring TwistedWires 0 5 2 0mm2 between the UPS cabinets and cabinet MOBs See Figure 4 3 and Figure 4 6fo...

Page 41: ...ce representative see paragraph 1 8 To install wiring 1 If not already installed install the LAN drop 2 Route and install the LAN and other cables to the appropriate Mini Slot cards See Figure 4 2 and...

Page 42: ...iring UPS 1 UPS 2 UPS 3 UPS 4 IN OUT IN OUT IN OUT IN OUT CAN BUS CAN BUS CAN BUS CAN BUS CN3 CN6 CN3 CN6 CN3 CN6 CN3 CN6 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 RJ 45 CABLE RJ 45 CABLE RJ 45 CABLE TERMIN...

Page 43: ...ppropriate terminals and review the wiring and termination requirements see paragraph 3 2 3 Table 4 3 Figure 4 3 and Figure 4 7 Figure 4 7 REPO Terminal Block Connector Assignments Table 4 3 REPO Conn...

Page 44: ...rmally closed REPO switch connect a jumper wire between pins 3 and 4 on the REPO terminal block 7 If you are installing multiple REPO switches wire additional switches in parallel with the first REPO...

Page 45: ...in advance usually a two week notice is required to reserve a preferred startup date 4 9 Completing the Installation Checklist The final step in installing the UPS system is completing the following I...

Page 46: ...ir conditioning equipment is installed and operating correctly The area around the installed UPS system is clean and dust free Eaton recommends that the UPS be installed on a level floor suitable for...

Page 47: ...UPS System Installation Eaton 93E UPS 300 400 kVA 380 400 415V Installation and Operation Manual 4 15 Notes...

Page 48: ...UPS System Installation This page intentionally left blank 4 16 Eaton 93E UPS 300 400 kVA 380 400 415V Installation and Operation Manual...

Page 49: ...Section 2 Operation...

Page 50: ......

Page 51: ...to Critical Load The Eaton 93E UPS is a continuous duty solid state transformer free three phase true online system that provides conditioned and uninterruptible AC power to the UPS system s output a...

Page 52: ...ical load The following paragraphs describe the differences in the UPS operating modes using block diagrams to show the power flow during each mode of operation 5 2 2 Standard Normal Mode During Stand...

Page 53: ...before turn on charge again If charge current is higher than 8A UPS will transfer to online mode from ESS mode HE mode if selected is a normal operating mode and not an alarm condition While the UPS i...

Page 54: ...unable to support the applied load The continuous static switch is wired in series with the backfeed protection contactor if fitted and together they are wired in parallel with the rectifier and inve...

Page 55: ...nd rectifier snubber components to the utility source If the input power fails to return or is not within the acceptance windows required for normal operation the battery continues discharging until a...

Page 56: ...in this section show the simplified internal structure of the UPS battery supply and basic maintenance bypass 5 3 Single UPS Unit System Oneline Configurations See Figure 5 5 93E 400 300 93E 400 400...

Page 57: ...per Static Switch Input Contactor Output Contactor Optional Backfeed Contactor AC Output to Critical Load Battery Converter Rectifier Inverter L1 L2 L3 N Pull Chain REPO Fuse Fuse Fuse Battery Contact...

Page 58: ...Understanding UPS Operation 5 8 Eaton 93E UPS 300 400 kVA 380 400 415V Installation and Operation Manual This page intentionally left blank...

Page 59: ...nd indicators and Figure 6 2 shows the UPS breaker Before starting the UPS ensure all installation tasks are complete and a preliminary startup has been performed by authorised service personnel The p...

Page 60: ...0 415V Installation and Operation Manual Figure 6 2 UPS Breaker 6 1 1 Control Panel The control panel is used to set up and control the UPS and to monitor UPS operation For a description of the UPS co...

Page 61: ...cators These colored light emitting diode LED lamps work with the alarm horn to let you know the operating status of the UPS Table 6 1 describes the status indicators 2 1 3 Table 6 1 Status Indicators...

Page 62: ...en see paragraph 6 2 6 System Event Horns The system event horn beeps to alert an operator that an event needing attention is taking place The horn cycles at a half second rate System Event Indicators...

Page 63: ...he information area contains data about UPS status and operations The menu bar shows the symbols of the available screens To select a screen highlight the screen symbol using the navigation pushbutton...

Page 64: ...name and meter subscripts change the password and view the firmware version numbers ESC Returns to Main Menu and Mimic screen from the Meters Events History Controls or Setup screens Returns to the ma...

Page 65: ...screen can be used to display user information and show the firmware versions installed Use the LEFT or RIGHT arrow pushbuttons to select the SETUP symbol on the main menu bar to display the Setup sc...

Page 66: ...urn to the System Setup screen press the ESC pushbutton Unit Name The Unit Name Setup screen allows a unit name to be entered Use the UP or DOWN arrow pushbutton to highlight Unit Name then press the...

Page 67: ...utton to highlight the command screen desired then press the RETURN pushbutton to display the command menu screen Use the or pushbutton to highlight the command desired Table 6 4 describes the control...

Page 68: ...dard Normal mode Battery Control Commands Use the up or down arrow pushbutton to highlight the command function desired then press the RETURN pushbutton to execute the command Charger Turns the batter...

Page 69: ...talled customer close the input feeder circuit breaker 6 If bypass input breaker is installed customer close the bypass input breaker 7 If the UPS contains an input breaker close the input breaker 8 C...

Page 70: ...TROLS symbol on the main menu bar The System Control screen is displayed 13 If not already selected select UPS on the System Control screen 14 On the UPS System Control screen select the LOAD OFF BYPA...

Page 71: ...screen select the BYPASS NORMAL command then press the RETURN pushbutton The UPS transfers to Normal mode If the power module is not available the system remains on bypass and an alarm sounds The NORM...

Page 72: ...trol panel 6 3 9 UPS and Critical Load Shutdown To perform maintenance or service on the critical load shut down power to the load 1 Turn off all equipment that is being powered by the UPS 2 Perform t...

Page 73: ...elect the CONTROLS symbol on the main menu bar The System Control screen is displayed 2 Select Battery on the System Control screen 3 On the Battery System Control screen select the CHARGING RESTING c...

Page 74: ...ess the RETURN pushbutton TheVerify Action screen is displayed providing a choice to proceed or abort the shutdown CAUTION All power to the critical load is lost when the LOAD OFF is selected in the f...

Page 75: ...step You should use this feature only when you want to de energise the critical load The following instructions are for the Eaton supplied REPO switch If a customer supplied REPO switch is used it may...

Page 76: ...an input breaker close the input breaker 7 If bypass input breaker is installed customer close the bypass input breaker 8 Close the door and secure the latch 9 Close all external battery breakers 10 O...

Page 77: ...e latch 9 Close the external battery breakers 10 Observe the UPS control panel display becoming active indicating logic power 11 Verify no alarms are active 12 Select the CONTROLS symbol on the main m...

Page 78: ...s present inside the UPS cabinet 6 4 5 Single UPS Shutdown To shut down the UPS 1 Open the MOB for the UPS being shut down 2 Select the CONTROLS symbol on the main menu bar The System Control screen i...

Page 79: ...eing restarted select the CONTROLS symbol on the main menu bar The System Control screen is displayed 9 If not already selected select UPS on the System Control screen 10 On the UPS System Control scr...

Page 80: ...en is displayed 2 Select Battery on the System Control screen 3 On the Battery System Control screen select the CHARGING RESTING command then press the RETURN pushbutton This UPS has a user initiated...

Page 81: ...erify Action screen is displayed providing a choice to proceed or abort the shutdown CAUTION All power to the critical load is lost when the LOAD OFF is selected in the following step You should use t...

Page 82: ...nd powers down the UPS immediately without asking for verification The UPS including Bypass remains off until restarted CAUTION All power to the critical load is lost when the REPO switch is activated...

Page 83: ...kVA 208 220V Installation and Operation Manual P 164000058 Rev 2 7 1 Chapter 7 Communication This chapter describes the communication features of the Eaton 9E UPS For terminal wiring information see...

Page 84: ...Communication This page intentionally left blank 7 2 Eaton 93E UPS 300 400 kVA 380 400 415V Installation and Operation Manual...

Page 85: ...harging source prior to connecting or disconnecting terminals Determine if the battery is inadvertently grounded If it is remove the source of the ground Contact with any part of a grounded battery ca...

Page 86: ...rameters as described in paragraph 6 2 Using the Control Panel 2 Check the UPS air filters located behind the front door and wash or replace as necessary See Figure 8 1 for filter location Contact an...

Page 87: ...performed only by authorised service personnel familiar with maintenance and servicing of the UPS system Contact an Eaton service representative for more information about service offerings 8 2 4 BATT...

Page 88: ...ser le m me nombre et mod le des batteries L limination des batteries est r glement e Consulter les codes locaux cet effet Do not discard the UPS or the UPS batteries in the trash This product contain...

Page 89: ...e input output environmental and battery specifications for the UPS Operating Input Voltage 380 400 415 Vac Input Voltage Range 190 330 276 478V 15 20 at 100 load 116 201 276 478V 50 20 at 50 load Ope...

Page 90: ...Regulation 0 1 Hz free running Synchronous to Bypass 4 Hz default setting Frequency Slew Rate 0 1 Hz per second Load Compatibility 0 9 PF Leading 0 7 PF Lagging Overload Capability 125 for 10 minutes...

Page 91: ......

Page 92: ...614 08137 00...

Reviews: