The UPS requires an input neutral connection. Make sure that an
input neutral is connected prior to energizing the UPS. If a 4-pole
automatic transfer switch is installed upstream of the UPS, it must
work with a break before make transition for the phase wires with a
minimum transfer time of 50 ms. Neutral must work with a make
before break transition.
Figure 15 and Figure 16 show the location of the UPS power cable
terminals.
Table 5. Input / output ratings and external cabling recommendations for the
Eaton 93E 15-80 kVA
Units
Rating 50/60 Hz
Basic unit rating
kVA
15 20 30 40
60
80
kW
13.5 18 27 36
54
72
Input and output voltage
Volts
380/
400/
415
380/
400/
415
380/
400/
415
380/
400/
415
380/
400/
415
380/
400/
415
A: AC Input to UPS rectifier (0.99
minimum PF)
Full load current plus battery
recharge current (3) phases
Amps 23 31 46 61
92 123
Conductor size
(phase L1, L2,
L3, N)
Recommended
mm
2
10 10 16 25
50
70
Maximum *
mm
2
25 25 25 25
70
70
B: AC input to UPS bypass (5-wire,
dual feed)
Full load current, (3) phases
Amps 22 29 43 58
87 115
Conductor size
(phase L1, L2,
L3, N)
Recommended
mm
2
10 10 16 25
50
70
Maximum *
mm
2
25 25 25 25
70
70
C: DC input from external battery
(384 V)
(1) positive, (1) negative
Total
Amps
39 52 77 103 155 206
Conductor size
Recommended
mm
2
16 16 25 35 2x35 2x50
Maximum *
mm
2
50 50 50 50 2x70 2x70