Eaton 93E UPS 15-80 kVA (380/400/415 V)
Installation and Operation Manual
© Eaton Corporation plc 2015. All rights reserved.
Revision: 001
Document ID: 614-01975-00
27 (133)
4.3
Site preparations
For the UPS system to operate at peak efficiency, the installation site
must meet the environmental parameters outlined in these instructions.
If the UPS needs to be operated at an altitude higher than 1 000 m
(3 300 ft) contact your service representative for important information
about high altitude operation. The operating environment must meet the
height, clearance, and environmental requirements specified.
4.3.1
Environmental and installation considerations
The UPS system installation must meet the following guidelines:
•
The system shall be installed indoors on a level floor suitable for
computer or electronic equipment.
•
The system shall be installed in a temperature and humidity
controlled area in which the dew point cannot be reached and that
is free of conductive contaminants.
Failure to follow guidelines may void your warranty.
The UPS equipment operating environment must meet the weight
requirements shown in Table 1, and the size requirements shown in
Figure 2 through Figure 6. Dimensions are in millimeters (inches).
Table 1. UPS cabinet weights
Mark
With package
kg (lb.)
Without package
kg (lb.)
Eaton 93E-15UI-N-64×9Ah-MBS
307 (677)
288 (635)
Eaton 93E-15UI-N-0-MBS
145 (320)
126 (278)
Eaton 93E-20I-N-64×9Ah-MBS
307 (677)
288 (635)
Eaton 93E-20I-N-0-MBS
145 (320)
126 (278)
Eaton 93E-30I-N-96×9Ah-MBS
405 (893)
386 (851)
Eaton 93E-30I-N-0-MBS
174 (384)
155 (342)
Eaton 93E-40I-N-128×9Ah-MBS
533 (1 175)
508 (1 120)
Eaton 93E-40I-N-0-MBS
216 (476)
194 (428)