UPS model
Phase cables
Rectifier, static
bypass and
maintenance
bypass input
fuse [A]
PE cable [mm
2
]
93PM-350(500)
2 x 185 mm
2
per
phase
630
185
93PM-400(500)
2 x 240 mm
2
per
phase
800
240
93PM-450(500)
2 x 240 mm
2
per
phase
800
240
93PM-500(500)
)
2 x 240 mm
2
per
phase
800
240
CAUTION
Make sure that prospective short-circuit current resulting at the UPS input terminals is
equal or less than conditional short-circuit current declared on the type plate of the UPS.
Table 4. Minimum recommended cable and fuse sizes for external battery bank
UPS model
Battery cable, pos. &
neg. line
Battery fuse [A]
93PM-100(400)
185 mm
2
per pole
315
93PM-150(400)
240 mm
2
per pole
400
93PM-200(400)
2 x 185 mm
2
per pole
630
93PM-250(400)
2 x 240 mm
2
per pole
700
93PM-300(400)
2 x 240 mm
2
per pole
800
93PM-350(400)
4 x 120 mm
2
per pole
1000
93PM-400(400)
4 x 185 mm
2
per pole
1250
93PM-100(500)
120 mm
2
per pole
250
93PM-150(500)
240 mm
2
per pole
400
93PM-200(500)
2 x 120 mm
2
per pole
500
93PM-250(500)
2 x 185 mm
2
per pole
630
93PM-300(500)
2 x 240 mm
2
per pole
800
93PM-350(500)
4 x 120 mm
2
per pole
1000
93PM-400(500)
4 x 120 mm
2
per pole
1000
93PM-450(500)
4 x 185 mm
2
per pole
1250
93PM-500(500)
4 x 185 mm
2
per pole
1250
Refer to national and local electrical codes for acceptable external wiring practices.
For information on rated and maximum currents for rated power and voltage, refer to the
Eaton 93PM UPS 100-500 kVA
User’s
and Installation Guide.
For the battery terminals in the 93PM with a separate battery option, refer to the Eaton
93PM UPS 100-500 kVA
User’s
and Installation Guide.
EN
66