If you do not obey these guidelines your warranty can become void.
CAUTION
If the unit is installed in an IT network, the voltage between neutral and
protective earth during normal operation must be less than 50 V (AC,
RMS), 71 V (AC, peak) or 120 V (DC).
CAUTION
This product can cause a DC current in the PE conductor. Where a
residual current-operated protective device (RCD) is used for protection
against electrical shock, only an RCD of Type B is allowed on the supply
side of this product.
The UPS equipment operating environment must meet the weight requirements
shown in
Table 4: UPS cabinet maximum weights
, and the size requirements
shown in
Table 5: UPS cabinet dimensions
Table 4: UPS cabinet maximum weights
UPS model
Shipping weight
[kg]
Installed weight
[kg]
Floor loading [kg/
m
2
]
93PM G2 50(200)
401
361
456
93PM G2 100(200)
444
404
510
93PM G2 150(200)
487
447
564
93PM G2 200(200)
530
490
619
93PM G2 240(240)
0.9 PF
530
490
619
93PM G2 50(300)
401
361
456
93PM G2 100(300)
444
404
510
93PM G2 150(300)
487
447
564
93PM G2 200(300)
530
490
619
93PM G2 250(300)
573
533
673