Provides remote monitoring through a Web browser interface, e-mail, and a
network management system (NMS) using SNMP and connects to a twisted-
pair Ethernet (10/100BaseT) network. The card also provides direct
integration of UPS information (meters and status) to a Building
Management System (BMS) using the Modbus RTU and TCP protocols as
well as BACnet protocols.
Figure 30: PX Gateway Card
•
Industrial Relay Card-MS
The MiniSlot Industrial Relay Card provides a way of connecting the UPS to
industrial and electrical monitoring systems. It also enables a wide range of
control applications by allowing up to 250 volts and 5 Amperes through its 5
relay connections. By connecting wires to the corresponding places in its
terminal blocks, you can choose Normally Open or Normally Closed setup for
each output.
For information on how to configure Industrial Relay Card-MS, see
Section
.
Figure 31: Industrial Relay Card-MS
© Eaton Corporation plc 2020. All rights reserved.
Revision: 001
Document ID: P-164000956
82 (141)
Eaton 93PM G2 UPS 50 – 360 kVA
User’s and Installation Guide