You can use a normally-closed or normally-open contact. If the state of the
contact changes from the state you specify as normal, a signal is issued. You can
connect this contact to equipment at your facility (such as a light or an alarm bell)
to let you know when an alarm is active on the UPS. This feature is useful if the
UPS is located in a remote area where the UPS horn may not be heard
immediately.
NOTE: Do not operate the contacts in excess of 30 VAC (RMS) and 30 VDC at 5
A maximum.
Figure 32: Output relay configurations
A) Normally closed (pins 1 and 3), B) Normally open (pins 2 and 3)
6.1.5
Configuring relays
The 93PM G2 offers one native relay output. Additionally, each of the four
MiniSlots can be equipped with a 5–relay adapter for additional relay outputs.
These instructions guide you through the relay configuration.
The relay configuration can be done via the display. See
Appendix A Relay
for available nodes that can be configured to relays.
The maximum voltage of the relay is 30 V. Examine the voltage and current
specifications of the other cards from the previous sections.
The process for relay configuration:
1.
In the home screen of the display, click the lock icon in the top right corner to
type in the service password.
© Eaton Corporation plc 2020. All rights reserved.
Revision: 001
Document ID: P-164000956
84 (141)
Eaton 93PM G2 UPS 50 – 360 kVA
User’s and Installation Guide