CAUTION
Make sure that prospective short-circuit current resulting at the input
terminals of the UPS is equal or less than conditional short-circuit
current declared on the type plate (and technical specification) of the
UPS. Also make sure that the prospective short-circuit current meets the
minimum requirements listed in Table
Minimum required short circuit
current ratings for AC source and battery supply
Table 9: Minimum required short circuit current ratings for AC source and battery
supply
UPS model
Minimum short circuit
current, AC ports [kA]
Minimum short circuit
current, battery port [kA]
93PM G2 xxx(yyy)
4
4
Table 10: Minimum recommended multi-core cable and fuse sizes for battery
connection
UPS model
Battery cable, pos. & neg.
line [mm
2
]
Battery fuse [A]
93PM G2 50(200)
50
200
93PM G2 100(200)
2 x 50 per pole
315
93PM G2 150(200)
2 x 95 per pole
500
93PM G2 200(200)
2 x 120 per pole
630
93PM G2 240(240)
2 x 185 per pole
700
93PM G2 50(300)
50
200
93PM G2 100(300)
2 x 50 per pole
315
93PM G2 150(300)
2 x 95 per pole
500
93PM G2 200(300)
2 x 120 per pole
630
93PM G2 250(300)
2 x 185 per pole
700
93PM G2 300(300)
2 x 240 per pole
800
93PM G2 360(360)
2 x 185 per pole
1000
© Eaton Corporation plc 2020. All rights reserved.
Revision: 001
Document ID: P-164000956
46 (141)
Eaton 93PM G2 UPS 50 – 360 kVA
User’s and Installation Guide