Table 12: Rated and maximum currents for rated power and voltage, rectifier
input and UPS output / bypass
UPS model
Rated voltage
[V]
Rectifier input
UPS output /
bypass
Rated current [A]
Rated
current
[A]
Maximum
current [A]
93PM G2 50
(300)
380
90
95
76
400
86
95
72
415
83
95
70
93PM G2 100
(300)
380
180
190
152
400
172
190
144
415
166
190
139
93PM G2 150
(300)
380
270
285
228
400
258
285
217
415
248
285
209
93PM G2 200
(300)
380
360
380
304
400
343
380
289
415
331
380
278
93PM G2 250
(300)
380
450
475
380
400
429
475
361
415
413
475
348
93PM G2 300
(300)
380
540
570
532
400
515
570
456
415
496
570
433
93PM G2 360
(360) 0.9 PF
380
540
570
547
400
540
570
520
415
537
570
501
NOTE: Maximum rectifier current calculated at the -15% voltage tolerance and
102% continuous overload.