Table 13: Rated and maximum currents for rated power and voltage, battery
UPS model
Battery
Rated current [A]
Maximum current* [A]
93PM G2 50(200)
114
139
93PM G2 100(200)
227
277
93PM G2 150(200)
341
416
93PM G2 200(200)
455
554
93PM G2 240(240) 0.9 PF
491
599
93PM G2 50(300)
114
139
93PM G2 100(300)
227
277
93PM G2 150(300)
341
416
93PM G2 200(300)
455
554
93PM G2 250(300)
568
693
93PM G2 300(300)
682
832
93PM G2 360(360) 0.9 PF
736
898
*) Maximum battery current calculated at rated load in the end of discharge of
VRLA battery (1.67 V per cell).
Table 14: UPS power cable terminations
Terminal function
Terminal
Function
AC input to UPS rectifier
X1
L1, L2, L3
AC input to bypass
X2
L1, L2, L3
UPS output
X3
L1, L2, L3
DC input from external
battery to UPS
X4
b, battery -
X5
N
Protective Earth
PE
PE