ECO Design Directive
2009/125/EC establishing a framework for the setting of
eco-design requirements for energy-related products
Batteries
2006/66/EC on batteries and accumulators and waste
batteries and accumulators
Packaging
94/62/EC on packaging and packaging waste
9.3
UPS environmental specifications
Table 33: UPS environmental specifications
Acoustic noise at 1 m
Rear exhaust
Top exhaust
74 dB(A)
77 dB(A)
Temperature range, operation
Eaton 93PM G2 xxx(200) and 93PM G2
xxx(300) models
+5 °C ... +40 °C
Recommended range *
+20 °C ... +25 °C
Temperature range, operation
Eaton 93PM G2 xxx(240) and 93PM G2
xxx(360) models
+5 °C ... +35 °C
Recommended range *
+20 °C ... +25 °C
Temperature range, storage and
transportation
-25 °C ... +55 °C
Relative Humidity
Recommended range *
5 % - 95 %
20 % - 60%
Condensation
No condensation allowed
Maximum rate of temperature change **
1.67 °C / 5min
Operating altitude
1000 m without derating
Up to 2000 m with 1% derating per each
additional 100 m above 1000 m
Over voltage category
OVC III
Pollution degree
PD 2
* ) For maximum lifetime for UPS and batteries, keep the environment in the
recommended range.
© Eaton Corporation plc 2020. All rights reserved.
Revision: 001
Document ID: P-164000956
116
(141)
Eaton 93PM G2 UPS 50 – 360 kVA
User’s and Installation Guide