Table 17: Recommended multi-core cable and fuse sizes for rectifier input,
bypass input and UPS output connections
UPS model
Phase cables [mm
2
]
Rectifier,
bypass and
mainte-
nance
bypass
input fuse
[A]
PE cable [mm
2
]
93PM G2 50
(200)
35
100
16
93PM G2 100
(200)
95
200
50
93PM G2 150
(200)
185
315
95
93PM G2 200
(200)
240
400
120
93PM G2 240
(240)
2 x 120
500
120
93PM G2 50
(300)
35
100
16
93PM G2 100
(300)
95
200
50
93PM G2 150
(300)
185
315
95
93PM G2 200
(300)
240
400
120
93PM G2 250
(300)
2 x 120
500
120
93PM G2 300
(300)
2 x 185
630
185
93PM G2 360
(360)
2 x 185
700
240
© Eaton Corporation plc 2020. All rights reserved.
Revision: 001
Document ID: P-164000956
74 (141)
Eaton 93PM G2 UPS 50 – 360 kVA