NOTE: UPS power upgrading is possible only if the sizing of the external cables
is sufficient. Alternatively, the external cabling must be upgraded as well. Fuses
are of the type gG.
Cable sizing is based on the standard IEC 60364-5-52 table B.52.2 and IEC
60364-5-54 table B.54.2. Sizing is for 70 ºC rated copper cables.
Table 20: Rated and maximum currents for rated power and voltage, rectifier
input and UPS output / bypass
UPS model
Rated
voltage [V]
Rectifier input
UPS output /
bypass
Rated current
[A]
Rated
current [A]
Maximum
current [A]
93PM G2 50(200)
380
90
95
76
400
86
95
72
415
83
95
70
93PM G2 100
(200)
380
180
190
152
400
172
190
144
415
166
190
139
93PM G2 150
(200)
380
270
285
228
400
258
285
217
415
248
285
209
93PM G2 200
(200)
380
360
380
304
400
343
380
289
415
331
380
278
93PM G2 240
(240) 0.9 PF
380
360
380
365
400
360
380
346
415
358
380
334
© Eaton Corporation plc 2020. All rights reserved.
Revision: 001
Document ID: P-164000956
76 (141)
Eaton 93PM G2 UPS 50 – 360 kVA
User’s and Installation Guide