Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 09
Table 1. Air Conditioning or Ventilation Requirements During Full Load Operation
Model
Rating
Input/Output
Voltage
Max Heat Dissipation
at 100% Load
kW [BTU/Hr]
Minimum
Required Cooling
Air Flow
Eaton 93PM 50 kW IAC-D with
Standard K13 Output Transformer
(non-TP1 efficiency)
50 kW
480/208
2.58 [8803]
Natural Convection
Eaton 93PM 50 kW IAC-D with
Input Autotransformer
and Standard K13 Output
Transformer
(non-TP1 efficiency)
50 kW
208/480 (input
transformer)
480/208 (output
transformer)
4.36 [14877]
320 liter/sec (678
cfm)
Eaton 93PM 100 kW IAC-D with
Standard K13 Output Transformer
(non-TP1 efficiency)
100 kW
480/208
4.18 [14268]
320 liter/sec (678
cfm)
Eaton 93PM 100 kW IAC-D with
Input Autotransformer
and Standard K13 Output
Transformer
(non-TP1 efficiency)
100 kW
208/480 (input
transformer)
480/208 (output
transformer)
5.62 [19176]
320 liter/sec (678
cfm)
Eaton 93PM 150 kW IAC-D with
Standard K13 Output Transformer
(non-TP1 efficiency)
150 kW
480/208
2.98 [10168]
320 liter/sec (678
cfm)
Eaton 93PM 200 kW IAC-D with
Standard K13 Output Transformer
(non-TP1 efficiency)
200 kW
480/208
3.50 [11943]
320 liter/sec (678
cfm)
The IAC-D operating environment must accommodate the weight requirements shown in
and the size
and space requirements shown in
and
through
Table 2. IAC-D Cabinet Weights
Model
Weight kg (lb)
Shipping
Installed
Point Loading
Eaton 93PM 50 kW IAC-D with output transformer
and two panelboards
567 (1251)
521 (1149)
4 at 130 (287)
Eaton 93PM 50 kW IAC-D with input and output
transformer and two panelboards
744 (1641)
698 (1539)
4 at 175 (385)
Eaton 93PM 100 kW IAC-D with output transformer
and two panelboards
674 (1487)
628 (1385)
4 at 157 (346)
Eaton 93PM 100 kW IAC-D with input and output
transformer and two panelboards
949 (2093)
903 (1991)
4 at 226 (498)