Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 09
35
WARNING
RISK OF INSTABILITY. Turning the jacking bolts unevenly may cause the cabinet to become unbalanced. To
prevent tipping the cabinet, raise the cabinet no more than 3 mm (1/8") above the floor (just enough to allow the
removal of the pallet skids). Failure to follow these instructions can result in serious injury or death.
5.
Turn each jacking bolt consecutively, two full turns, until the pallet skids clear the floor by approximately
3 mm (1/8").
NOTE
In the following step the center supports will drop away from the cabinet and the pallet
skids when the skids are removed.
6.
Remove the hardware loosened in
. Pull the two pallet skids out from under the left, right, front,
rear, and two center supports. Recycle the pallet skids, supports, and hardware in a responsible manner.
CAUTION
CABINET MAY FALL. Do not loosen the hardware attaching the front supports to the cabinet base. The cabinet
must be lowered by the jacking bolts before the supports can be removed.
7.
Carefully and evenly
lower the cabinet by turning each jacking bolt consecutively two full turns
(maximum)
until the casters contact the floor and the cabinet is no longer supported by the jacking bolts.
8.
After the IAC-D is resting on the floor, remove the jacking bolts and floor protectors. Recycle them in a
responsible manner.
9.
Remove the cabinet support bolts fastening the left, right, front, and rear supports together (see
).
10. Remove the cabinet mounting bolts holding the left, right, front, and rear supports to the cabinet base and
remove the supports (see
11. If installing the cabinet permanently, retain the cabinet mounting bolts; otherwise, recycle the bolts along
with the support brackets in a responsible manner.
12. Close the door and secure the latch.
13. If the leveling feet are not retracted, turn all four leveling feet until they are retracted as far into the cabinet
as possible.
NOTE
The IAC-D may be located to either the right or left of the UPS cabinet. The
recommended location is to the left of the UPS cabinet. This procedure assumes the
IAC-D is located to the left of the UPS cabinet.
14. If line-up-and-match installation, remove the rectangular knockout on the bottom front side of the UPS and
the IAC-D (see
).
CAUTION
To prevent tipping when rolling the cabinet, push the cabinet from the rear whenever possible.
15. Roll the IAC-D to the line-up-and-match installation location on the left side of the UPS cabinet making sure
the doors are flush with each other or to the standalone installation location.
16. Lower the IAC-D cabinet’s feet and using a level, adjust the cabinet height accordingly until the cabinet is
level.
17. Locate the top splice bracket shipped with the IAC-D.