Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 09
Table 3. IAC-D Cabinet Clearances
From Front of Cabinet
914.4 mm (36") working space
From Top of Cabinet with Top Exhaust (50 kW Zone 1 – see
203 mm (8") minimum clearance for ventilation
From Top of Cabinet with Top Exhaust (100 kW, 150 kW, and 200
kW, 480V/208V Zone 1 – see
or
457.2 mm (18") minimum clearance for ventilation
and working space
From Top of Cabinet with Top Exhaust (50 kW and 100 kW, 208V/
208V Zone 1 – see
or
)
457.2 mm (18") minimum clearance for ventilation
and working space
From Top of Cabinet with rear service access (Zone 2 – see
or
)
Can be less than 457.2 mm (18")
From Back of Cabinet with Rear Exhaust (50 kW and 100 kW, 480V/
208V)
203 mm (8") minimum clearance for ventilation
From Back of Cabinet with Rear Exhaust (150 kW and 200 kW,
480V/208V)
457.2 mm (18") minimum clearance for ventilation
From Back of Cabinet with Rear Exhaust (50 kW and 100 kW, 208V/
208V)
457.2 mm (18") minimum clearance for ventilation
From Back of Cabinet – Seismic Installation
914.4 mm (36") working space
From Right Side of Cabinet
None Required
From Left Side of Cabinet
None Required