Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 09
27
Table 8. External Input Power Cable Terminations for the Eaton 93PM IAC-D (480V/208V) (Continued)
Terminal
Function
kW
Rating
Terminal
Function
Number and Size of
Pressure Termination
(AWG or kcmil)
Tightening
Torque
Nm (lb in)
Type and
Size Screw
Customer
Ground
—
G
Ground
1 – #14-1/0
5.1 (45)
Slotted
Inter-Cabinet
Bonding
—
G
Bonding
1 – #14-1/0
5.1 (45)
Slotted
Table 9. External Input Power Cable Terminations for the Eaton 93PM IAC-D (208V/208V)
Terminal
Function
kW
Rating
Terminal
Function
Number and Size of
Pressure
Termination
(AWG or kcmil)
Tightening
Torque
Nm (lb in)
Type and
Size Screw
208 VAC Input to
IAC-D
from Utility Source
50
A
Phase A
2 – #6–300
31 (275)
5/16” Hex
B
Phase B
2 – #6–300
31 (275)
5/16” Hex
C
Phase C
2 – #6–300
31 (275)
5/16” Hex
480 VAC Output
to UPS from
IAC-D UPS Input
Breaker
50
UIB-2
Phase A
1 – #14-1/0
5.6 (50)
5/16” Hex
UIB-4
Phase B
1 – #14-1/0
5.6 (50)
5/16” Hex
UIB-6
Phase C
1 – #14-1/0
5.6 (50)
5/16” Hex
480 VAC Input to
IAC-D from UPS
50
A
Phase A
1 – #6-500
56.5 (500)
5/16” Hex
B
Phase B
1 – #6-500
56.5 (500)
5/16” Hex
C
Phase C
1 – #6-500
56.5 (500)
5/16” Hex
208 VAC Input to
IAC-D
from Utility Source
100
A
Phase A
2 – #6–300
31 (275)
5/16” Hex
B
Phase B
2 – #6–300
31 (275)
5/16” Hex
C
Phase C
2 – #6–300
31 (275)
5/16” Hex
480 VAC Output to
UPS from
IAC-D UPS Input
Breaker
100
UIB-2
Phase A
1 – #4-4/0
5.6 (50)
5/16” Hex
UIB-4
Phase B
1 – #4-4/0
5.6 (50)
5/16” Hex
UIB-6
Phase C
1 – #4-4/0
5.6 (50)
5/16” Hex
480 VAC Input to
IAC-D from UPS
100
A
Phase A
1 – #6-500
56.5 (500)
5/16” Hex
B
Phase B
1 – #6-500
56.5 (500)
5/16” Hex
C
Phase C
1 – #6-500
56.5 (500)
5/16” Hex
Customer Ground
—
G
Ground
2 – #14-1/0
5.1 (45)
Slotted
Inter-Cabinet
Bonding
—
G
Bonding
2 – #14-1/0
5.1 (45)
Slotted