Eaton 93PM Integrated Accessory Cabinet-Tie (50 kW and 100 kW IAC-T) Installation and Operation Manual P-164000371—Rev 05
•
Maximum Relative Humidity: 5–95%, noncondensing
The IAC-T operating environment must meet the weight requirements shown in
and the size
requirements shown in
through
. Dimensions are in millimeters (inches).
Table 1. IAC-T Weights
Model
Weight kg (lb)
Shipping
Installed
Point Loading
Eaton 93PM 50 kW IAC-T – Four MOBs with MIS and
MBP
230 (506)
208 (458)
4 at 52.0 (114.5)
Eaton 93PM 100 kW IAC-T – Four MOBs with MIS and
MBP
230 (506)
208 (458)
4 at 52.0 (114.5)
The IAC-T uses convection cooling to regulate internal component temperature. Air inlets are in the front of the
cabinet and outlets are on top or in the back of the cabinet. Allow clearance in front of and on top or in back of
the cabinet for proper air circulation. The clearances required around the IAC-T are shown in
Table 2. IAC-T Cabinet Clearances
From Top of Cabinet with Rear Exhaust Option
304.8 mm (8") working space
From Top of Cabinet with Top Exhaust Option
304.8 mm (8") minimum clearance for ventilation
From Front of Cabinet
914.4 mm (36") working space
From Back of Cabinet with Top Exhaust Option
None Required
From Back of Cabinet with Rear Exhaust Option
203.2 mm (8") minimum clearance for ventilation
From Back of Cabinet – Seismic Installation
914.4 mm (36") working space
From Right Side of Cabinet
None Required
From Left Side of Cabinet
None Required