Eaton 93PM Integrated Accessory Cabinet-Tie (50 kW and 100 kW IAC-T) Installation and Operation Manual P-164000371—Rev 05
23
Table 12. External Input Power Cable Terminations for the Eaton 93PM 50 kW IAC-T 1+1, 2+0, 2+1, 3+0, 3+1, and 4+0
Parallel Configurations – No MIS or MBP (Continued)
Terminal Function
Terminal
Function
Number and Size of
Pressure Termination
(AWG or kcmil)
Tightening
Torque Nm (lb
in)
Size Screw and
Type
MOB2–5C
Phase C
1 – 4–4/0
13.5 (120)
3/16” Hex
TBG
Ground
2 – 14– 1/0
5.1 (45)
Slotted
AC Input to MOB 3 from
UPS 3 (if installed)
MOB3–1A
Phase A
1 – 4–4/0
13.5 (120)
3/16” Hex
MOB3–3B
Phase B
1 – 4–4/0
13.5 (120)
3/16” Hex
MOB3–5C
Phase C
1 – 4–4/0
13.5 (120)
3/16” Hex
TBG
Ground
2 – 14– 1/0
5.1 (45)
Slotted
AC Input to MOB 4 from
UPS 4 (if installed)
MOB4–1A
Phase A
1 – 4–4/0
13.5 (120)
3/16” Hex
MOB4–3B
Phase B
1 – 4–4/0
13.5 (120)
3/16” Hex
MOB4–5C
Phase C
1 – 4–4/0
13.5 (120)
3/16” Hex
TBG
Ground
2 – 14– 1/0
5.1 (45)
Slotted
AC Output to Critical Load
Load Bus A
Phase A
2 – 6–350
42 (375)
5/16” Hex
Load Bus B
Phase B
2 – 6–350
42 (375)
5/16” Hex
Load Bus C
Phase C
2 – 6–350
42 (375)
5/16” Hex
Building and Load Ground
TBG
Ground
6 – 14–1/0
5.1 (45)
Slotted
, and
show the location of the IAC-T power cable terminals.
Table 13. External Input Power Cable Terminations for the Eaton 93PM 50 kW IAC-T 1+1, 2+0, 2+1, 3+0, 3+1, and 4+0
Parallel Configurations – with MIS
Terminal Function
Terminal
Function
Number and Size of
Pressure Termination
(AWG or kcmil)
Tightening
Torque Nm (lb
in)
Size Screw and Type
AC Input to MOB 1 from
UPS 1
MOB1–1A
Phase A
1 – 4–4/0
13.5 (120)
3/16” Hex
MOB1–3B
Phase B
1 – 4–4/0
13.5 (120)
3/16” Hex
MOB1–5C
Phase C
1 – 4–4/0
13.5 (120)
3/16” Hex
GND
Ground
2 – 14– 1/0
5.1 (45)
Slotted
AC Input to MOB 2 from
UPS 2
MOB2–1A
Phase A
1 – 4–4/0
13.5 (120)
3/16” Hex
MOB2–3B
Phase B
1 – 4–4/0
13.5 (120)
3/16” Hex
MOB2–5C
Phase C
1 – 4–4/0
13.5 (120)
3/16” Hex
TBG
Ground
2 – 14– 1/0
5.1 (45)
Slotted
AC Input to MOB 3 from
UPS 3 (if installed)
MOB3–1A
Phase A
1 – 4–4/0
13.5 (120)
3/16” Hex
MOB3–3B
Phase B
1 – 4–4/0
13.5 (120)
3/16” Hex
Summary of Contents for 93PM IAC-T Series