Eaton 93PM Integrated Accessory Cabinet-Tie (50 kW and 100 kW IAC-T) Installation and Operation Manual P-164000371—Rev 05
27
Table 16. External Input Power Cable Terminations for the Eaton 93PM 100 kW IAC-T 1+1, 2+0, 2+1, 3+0, 3+1, and 4+0
Parallel Configurations – with MIS (Continued)
Terminal Function
Terminal
Function
Number and Size of
Pressure Termination
(AWG or kcmil)
Tightening
Torque Nm (lb
in)
Size Screw and Type
AC Input to MOB 3
from UPS 3 (if
installed)
MOB3–1A
Phase A
1 – 4–4/0
13.5 (120)
3/16” Hex
MOB3–3B
Phase B
1 – 4–4/0
13.5 (120)
3/16” Hex
MOB3–5C
Phase C
1 – 4–4/0
13.5 (120)
3/16” Hex
TBG
Ground
2 – 14– 1/0
5.1 (45)
Slotted
AC Input to MOB 4
from UPS 4 (if
installed)
MOB4–1A
Phase A
1 – 4–4/0
13.5 (120)
3/16” Hex
MOB4–3B
Phase B
1 – 4–4/0
13.5 (120)
3/16” Hex
MOB4–5C
Phase C
1 – 4–4/0
13.5 (120)
3/16” Hex
TBG
Ground
2 – 14– 1/0
5.1 (45)
Slotted
AC Output to Critical
Load
(1+1)
MIS– 2A
Phase A
1 – 4–4/0
13.5 (120)
3/16” Hex
MIS– 4B
Phase B
1 – 4–4/0
13.5 (120)
3/16” Hex
MIS– 6C
Phase C
1 – 4–4/0
13.5 (120)
3/16” Hex
AC Output to Critical
Load
(2+0 and 2+1)
MIS– 2A
Phase A
1 – 4–350
28.2 (250)
5/16” Hex
MIS– 4B
Phase B
1 – 4–350
28.2 (250)
5/16” Hex
MIS– 6C
Phase C
1 – 4–350
28.2 (250)
5/16” Hex
AC Output to Critical
Load
(3+0, 3+1, and 4+0)
MIS– 2A
Phase A
1 – 2 stud bus bar
mounting
12.2 (108)
M8 Stud with 13 mm
Hex Nut
MIS– 4B
Phase B
1 – 2 stud bus bar
mounting
12.2 (108)
M8 Stud with 13 mm
Hex Nut
MIS– 6C
Phase C
1 – 2 stud bus bar
mounting
12.2 (108)
M8 Stud with 13 mm
Hex Nut
Building and Load
Ground
TBG
Ground
6 – 14–1/0
5.1 (45)
Slotted
The torque values listed for the M8 studs in
are the maximum allowable. Tightening further will risk
breaking or twisting the stud.
, and
show the location of the IAC-T power cable terminals.
Table 17. External Input Power Cable Terminations for the Eaton 93PM 100 kW IAC-T 1+1, 2+0, 2+1, 3+0, 3+1, and 4+0
Parallel Configurations – with MIS and MBP
Terminal Function
Termi-
nal
Func-
tion
Number and Size of
Pressure Termination
(AWG or kcmil)
Tightening
Torque Nm
(lb in)
Size Screw and
Type
AC Input to MOB 1 from UPS 1
MOB1–
1A
Phase A
1 – 4–4/0
13.5 (120)
3/16” Hex
MOB1–
3B
Phase B
1 – 4–4/0
13.5 (120)
3/16” Hex