Eaton 93PM Integrated Accessory Cabinet-Tie (50 kW and 100 kW IAC-T) Installation and Operation Manual P-164000371—Rev 05
23. Secure the cabinet to the floor with customer-supplied hardware.
24. Proceed to paragraph
Installing IAC-T External Power Wiring
25. Locate the front and back floor mounting brackets from the optional floor mounting kit.
26. Using the cabinet mounting bolts from the kit, install the floor mounting brackets to the front and rear of
the UPS with the angle facing outward.
27. Secure the cabinet to the floor with customer-supplied hardware.
NOTE
Black cover dots are provided, if side mounting bracket holes need to be covered for
aesthetic reasons.
28. Locate the black cover dots from the parts kit and install over the left and right side bracket mounting
holes.
29. Proceed to paragraph
Installing IAC-T External Power Wiring
Figure 10. Line-Up-and-Match Wiring Access Locations
Inter-cabinet wiring access
to route interface wiring
between cabinets.
Inter-cabinet wiring access
knockouts. Remove knockouts
as required to route power
wiring between cabinets.
Left Side View
Right Side View