Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (50 kW and 100 kW SIAC-B) Installation and Operation Manual P-164000230—Rev 09
11
Table 2. Eaton 93PM 100 kW with Left or Right-Mounted Three-Wire SIAC-B Cabinet Weights
Model
Weight kg (lb)
Shipping
Installed
Point
Loading
93PM-100-1 Capacity UPS with 4-Breaker SIAC-B
477 [1051]
446 [984]
6 at 74 [164]
93PM-100-2 Capacity UPS with 4-Breaker SIAC-B
541 [1191]
510 [1124]
6 at 85 [187]
93PM-100-1 Redundant UPS with 4-Breaker SIAC-B
483 [1064]
452 [997]
6 at 75 [166]
93PM-100-2 Redundant UPS with 4-Breaker SIAC-B
547 [1204]
516 [1137]
6 at 86 [190]
93PM-100-3 Redundant UPS with 4-Breaker SIAC-B
611 [1345]
580 [1278]
6 at 97 [213]
93PM-100-1 Capacity UPS with Empty SIAC-B (Top Entry)
450 [991]
419 [924]
6 at 70 [154]
93PM-100-2 Capacity UPS with Empty SIAC-B (Top Entry)
514 [1131]
483 [1064]
6 at 81 [177]
93PM-100-1 Redundant UPS with Empty SIAC-B (Top Entry)
456 [1004]
425 [937]
6 at 71 [156]
93PM-100-2 Redundant UPS with Empty SIAC-B (Top Entry)
520 [1144]
489 [1077]
6 at 82 [180]
93PM-100-3 Redundant UPS with Empty SIAC-B (Top Entry)
583 [1285]
552 [1218]
6 at 92 [203]
Table 3. Eaton 93PM 50 kW with Left or Right-Mounted Four-Wire SIAC-B Cabinet Weights
Model
Weight kg (lb)
Shipping
Installed
Point Loading
93PM-50-1 Capacity UPS with 4-Breaker SIAC-B – 0 Battery
460 [1014]
429 [947]
6 at 72 [158]
93PM-50-1 Capacity UPS with 4-Breaker SIAC-B – 3 Battery
880 [1939])
849 [1872]
6 at 142 [312]
93PM-50-1 Capacity UPS with 4-Breaker SIAC-B – 4 Battery
984 [2170]
953 [2103]
6 at 159 [351]
93PM-50-1 Redundant UPS with 4-Breaker SIAC-B – 0 Battery
476 [1049]
445 [982]
6 at 74 [164]
93PM-50-2 Redundant UPS with 4-Breaker SIAC-B – 0 Battery
540 [1190]
509 [1123]
6 at 85 [187]
93PM-50-1 Capacity UPS with Empty SIAC-B (Top Entry) – 0 Battery
433 [954]
402 [887]
6 at 67 [148]
93PM-50-1 Capacity UPS with Empty SIAC-B (Top Entry) – 3 Battery
852 [1879]
821 [1812]
6 at 137 [302]
93PM-50-1 Capacity UPS with Empty SIAC-B (Top Entry) – 4 Battery
957 [2110]
926 [2043]
6 at 154 [341]
93PM-50-1 Redundant UPS with Empty SIAC-B (Top Entry) – 0 Battery
449 [989]
418 [922]
6 at 70 [154]
93PM-50-2 Redundant UPS with Empty SIAC-B (Top Entry) – 0 Battery
513 [1130]
482 [1063]
6 at 80 [177]