Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (50 kW and 100 kW SIAC-B) Installation and Operation Manual P-164000230—Rev 09
Table 5. External Power Wiring Recommendations: Eaton 93PM 50 kW and 100 kW Three-Wire SIAC-B – Two and
Three Breaker Maintenance Bypass
Basic Unit Rating
Units
Rating 60 Hz
kW
50
100
Input/Output Voltage
Volts
480/480
480/480
AC Input to Maintenance Bypass
(3) Phases, (1) Ground
A
Maximum Amps
73
146
Minimum Conductor Size (Phase A, B, and C)
Number per Phase
AWG or kcmil
(each)
3
(1)
3/0
(1)
Minimum Conductor Size (Ground)
Number per Phase
—
AWG or kcmil
(each)
8
(1)
6
(1)
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Ground
C
Maximum Amps
60
120
Minimum Conductor Size (Phase A, B, and C)
Number per Phase
AWG or kcmil
(each)
4
(1)
2/0
(1)
Minimum Conductor Size (Ground)
Number per Phase
—
AWG or kcmil
(each)
8
(1)
6
(1)
Building and Inter-Cabinet Ground
Minimum Conductor Size (Ground)
Number per Phase
—
AWG or kcmil
(each)
8
(1)
6
(1)
NOTE
Callout letters
A
and
C
map to
,
, and
.