Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (50 kW and 100 kW SIAC-B) Installation and Operation Manual P-164000230—Rev 09
Table 9. External Input Power Cable Terminations for the Eaton 93PM 50 kW Three or Four-Wire SIAC-B
Terminal Function
Termi-
nal
Func-
tion
Number and Size of
Pressure Termination
(AWG or kcmil)
Tightening
Torque Nm
(lb in)
Size Screw and
Type
AC Input to RIB – Source 1
(4-breaker version only)
E1
(RIB–1)
Phase A
1 – #4–350
19.9 (177)
5/16" Hex
E2
(RIB–3)
Phase B
1 – #4–350
19.9 (177)
5/16" Hex
E3
(RIB–5)
Phase C
1 – #4–350
19.9 (177)
5/16" Hex
AC Input to Maintenance Bypass –
Source 2
E6
Phase A
1 – #6–250
31 (275)
5/16" Hex
E7
Phase B
1 – #6–250
31 (275)
5/16" Hex
E8
Phase C
1 – #6–250
31 (275)
5/16" Hex
(4-Wire version only)
E12
Neutral
2 – #6–300
31 (275)
5/16" Hex
AC Output to Critical Load
E9
Phase A
2 – #6–250
31 (275)
5/16" Hex
E10
Phase B
2 – #6–250
31 (275)
5/16" Hex
E11
Phase C
2 – #6–250
31 (275)
5/16" Hex
(4-Wire version only)
E12
Neutral
2 – #6–300
31 (275)
5/16" Hex
Building, Inter-Cabinet, and Load
Ground
TBG
Ground
6 – #14–1/0
5.1 Nm (45)
Slotted
The power wiring terminals for the Eaton 93PM 50 kW Four-Wire SIAC-B and Eaton 93PM 100 kW Four-Wire
SIAC-B are pressure terminations. The power wiring connections for this equipment are UL and CSA rated. See
for external power cable terminations.
or shows the location of the SIAC-B power cable terminals.