Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (50 kW and 100 kW SIAC-B) Installation and Operation Manual P-164000230—Rev 09
63
C
Chhaapptteerr 66 S
SIIA
AC
C--B
B O
Oppeerraattiinngg IInnssttrruuccttiioonnss
This section describes how to operate the Sidecar Integrated Accessory Cabinet-Bypass (SIAC-B).
NOTE 1
Before using the SIAC-B, ensure all installation tasks are complete and a preliminary
startup has been performed by authorized service personnel. The preliminary startup
verifies all electrical interconnections to ensure the installation was successful and the
system operates properly.
NOTE 2
Read this section of the manual and have thorough knowledge of UPS and SIAC-B
operation before attempting to operate any of the controls.
66..11
S
Siiddeeccaarr IInntteeggrraatteedd A
Acccceessssoorryy C
Caabbiinneett--B
Byyppaassss
66..11..11
C
Ciirrccuuiitt B
Brreeaakkeerrss
or
identifies and shows the location of the circuit breakers in the SIAC-B. The descriptions
provide a brief overview of the SIAC-B breaker use.
•
Maintenance Bypass Breaker
– The Maintenance Bypass Breaker (MBP) transfers the load from the UPS
output to the bypass input feeder.
•
Maintenance Isolation Breaker
– The Maintenance Isolation Breaker (MIS) isolates the UPS from the
bypass feed and the load.
•
Bypass Input Breaker
– (Optional – only three and four breaker configurations) The Bypass Input Breaker
(BIB) provides a single point of input power control to the UPS on single-feed systems or bypass input
power control to the UPS on dual-feed systems. Using the BIB easily removes power from the UPS for
servicing.
•
Rectifier Input Breaker
– (Optional – only four breaker configurations) The optional Rectifier Input Breaker
(RIB) (four-breaker version only) provides a single point of rectifier input power control to the UPS on dual-
feed systems and easily removes power from the UPS for servicing.
66..11..22
U
Ussiinngg tthhee U
UP
PS
S w
whheenn aann S
SIIA
AC
C--B
B iiss IInnssttaalllleedd
To operate the SIAC-B:
1.
Remove the screw securing the bottom of the SIAC-B front panel. Lift the panel straight up to remove it
from the panel hanger bracket at the top of the cabinet. Retain screw for later use.
2.
Close the SIAC-B bypass input feeder circuit breaker.
3.
If an BIB is installed, close the SIAC-B bypass input feeder breaker.
4.
If an RIB is installed, close the SIAC-B rectifier input feeder breaker.
5.
Verify that the SIAC-B circuit breakers are set as follows (see
or
for breaker locations):
MBP
OPEN
MIS
CLOSED
BIB (if installed)
CLOSED
RIB (if installed)
CLOSED
6.
Start the UPS. Refer to the applicable Eaton 93PM UPS Installation and Operation manual listed in
paragraph
, for UPS operating procedures.