Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (50 kW and 100 kW SIAC-B) Installation and Operation Manual P-164000230—Rev 09
29
Table 10. External Input Power Cable Terminations for the Eaton 93PM 100 kW Three or Four-Wire SIAC-B
Terminal Function
Termi-
nal
Func-
tion
Number and Size of
Pressure Termination
(AWG or kcmil)
Tightening
Torque Nm
(lb ft)
Size Screw and
Type
AC Input to RIB – Source 1
(4-breaker version only)
E1
(RIB–1)
Phase A
1 – #4–350
19.9 (177)
5/16" Hex
E2
(RIB–3)
Phase B
1 – #4–350
19.9 (177)
5/16" Hex
E3
(RIB–5)
Phase C
1 – #4–350
19.9 (177)
5/16" Hex
AC Input to Maintenance Bypass –
Source 2
E6
Phase A
1 – #6–250
31 (275)
5/16" Hex
E7
Phase B
1 – #6–250
31 (275)
5/16" Hex
E8
Phase C
1 – #6–250
31 (275)
5/16" Hex
(4-Wire version only)
E12
Neutral
2 – #6–300
31 (275)
5/16" Hex
AC Output to Critical Load
E9
Phase A
2 – #6–250
31 (275)
5/16" Hex
E10
Phase B
2 – #6–250
31 (275)
5/16" Hex
E11
Phase C
2 – #6–250
31 (275)
5/16" Hex
(4-Wire version only)
E12
Neutral
2 – #6–300
31 (275)
5/16" Hex
Building, Inter-Cabinet, and Load
Ground
TBG
Ground
6 – #14–1/0
5.1 Nm (45)
Slotted
33..33..44
S
SIIA
AC
C--B
B IInntteerrffaaccee W
Wiirriinngg P
Prreeppaarraattiioonn
Control wiring for features and options should be connected at the customer interface terminal block located
inside the SIAC-B.
Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is
required.
Read and understand the following notes while planning and performing the installation:
•
Use Class 1 wiring methods (as defined by the NEC) for interface wiring from 30V to 600V. The wire
should be rated for 600V, 1A minimum. 12 AWG maximum wire size.
•
Use Class 2 wiring methods (as defined by the NEC) for interface wiring up to 30V. The wire should be
rated for 24V, 1A minimum.
•
Use twisted-pair wires for each input and return or common.
•
All interface wiring and conduit is to be supplied by the customer.
•
Interface wiring can be installed using the inter-cabinet wiring access pass-through or by routing wiring
through conduit between cabinets.
•
Install the interface wiring in separate conduit from the power wiring.