Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (50 kW and 100 kW SIAC-B) Installation and Operation Manual P-164000230—Rev 09
43
2.
Reconnect the UPS output, the UPS bypass input, and if an RIB is installed the UPS rectifier input tagged
wiring to the respective UPS terminals. Refer to the applicable Eaton 93PM UPS Installation and Operation
manual, listed in paragraph
, for terminal locations and requirements.
3.
If installing a four-wire SIAC-B, reconnect the tagged neutral wiring to the respective UPS terminals. Refer
to the applicable Eaton 93PM UPS Installation and Operation manual, listed in paragraph
, for terminal locations and requirements.
4.
Reconnect the UPS MBP interface harness connector to the UPS MBP interface terminal block connector
(see XRef Fig interface location or XRef Fig interface location, and XRef Fig interface detail).
5.
Refer to the applicable Eaton 93PM UPS Installation and Operation manual, listed in paragraph
, to complete the mechanical installation of the UPS and SIAC-B. After completing
the mechanical installation return to paragraph .
44..66
U
Unnllooaaddiinngg tthhee FFaaccttoorryy IInnssttaalllleedd S
SIIA
AC
C--B
B ffrroom
m tthhee P
Paalllleett aanndd M
Meecchhaanniiccaall IInnssttaallllaattiioonn
The SIAC-B is attached to and directly integrated with the UPS cabinet at the factory. Refer to the applicable
Eaton 93PM UPS Installation and Operation manual listed in paragraph
for unloading
and mechanical installation instructions.
After completing the unloading and installation of the UPS with the attached SIAC-B, proceed to paragraph
Installing SIAC-B External Power Wiring
.
44..77
TTw
woo--H
Hoollee B
Baarrrreell LLuugg TTeerrm
miinnaattiioonnss ttoo B
Buuss B
Baarr IInnssttaallllaattiioonn
Paragraph
Installing SIAC-B External Power Wiring
may require connecting input and output power wiring
using 2-hole barrel lugs. See
for the hardware sequence when installing the lugs to the bus bars.
Tighten the bolt to the torque value listed in
or
.
Proceed to paragraph
Installing SIAC-B External Power Wiring
NOTE
Conical washers are special purpose washers that look similar to flat washers, except
for a slight conical shape. When installing conical washers, the top of the dome should
be next to the bolt head and the base of the washer should be against a flat surface such
as a bus bar, flat washer, or large terminal.
Summary of Contents for 93PM IBC-L