Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (50 kW and 100 kW SIAC-B) Installation and Operation Manual P-164000230—Rev 09
1
C
Chhaapptteerr 11 IInnttrroodduuccttiioonn
The Eaton
®
93PM 50 kW and 100 kW Three-Wire Sidecar Integrated Accessory Cabinet-Bypass (SIAC-B) is
designed for use with the Eaton 93PM 50 kW and 100 kW Three-Wire UPS systems. The Eaton 93PM 50 kW
and 100 kW Four-Wire SIAC-B is designed for used with the Eaton 93PM 50 kW and 100 kW Four-Wire UPS
systems. The SIAC-B provides maintenance bypass functions with configurable features, enabling adaptation
and expansion without costly electrical rework.
NOTE
Startup and operational checks must be performed by an authorized Eaton Customer
Service Engineer, or the warranty terms specified on the product's resources page
become void. See
for details. This service is offered as part of the
sales contract for the UPS. Contact an Eaton service representative in advance (a
minimum two-week notice is required) to reserve a preferred startup date.
11..11
FFeeaattuurreess
The following descriptions provide a brief overview of the SIAC-B functions:
•
Two breaker configuration: The bypass sidecar contains only a Maintenance Bypass (MBP) and
Maintenance Isolation (MIS) breaker. This allows Maintenance bypass for system repair or maintenance.
The critical load is NOT protected in the Maintenance bypass mode.
•
Three breaker configuration (used with single-feed systems): Maintenance Bypass (MBP) and
Maintenance Isolation (MIS) breakers, and a Bypass Input Breaker (BIB) enable power to completely
bypass the UPS. The UPS can then be safely serviced or replaced without interrupting power to critical
systems.
•
Four breaker configuration (used with dual-feed systems): Maintenance Bypass (MBP) and Maintenance
Isolation (MIS) breakers, and a Bypass Input Breaker (BIB) enable power to completely bypass the UPS. A
Rectifier Input Breaker (RIB) provides a convenient method for removing power from the UPS when using
the maintenance bypass to supply the load. The UPS can then be safely serviced or replaced without
interrupting power to critical systems.
and
, show the SIAC-B mounted to the UPS cabinet.
11..22
IInnssttaallllaattiioonn FFeeaattuurreess
The SIAC-B is housed in a single cabinet factory attached to and directly integrated with the UPS cabinet and
must be ordered mounted on either the left or right side of the UPS. The SIAC-B matches the UPS cabinet in
style and color. It has safety shields behind the removable front panel for hazardous voltage protection. Power
wiring between the UPS and SIAC-B are factory installed. Output power wiring to the critical load is routed
using external conduit.