background image

Eaton 93PM Cabinet Seismic Tie Strap Installation Instructions

Use these instructions to install cabinet top and rear seismic tie straps to secure the Uninterruptible Power 
Supply (UPS) and Sidecar Integrated Accessory Cabinet (SIAC), and when installed in a line-up-and-match 
configuration the Integrated Battery Cabinets (IBCs) and Integrated Accessory Cabinets (IACs).

To install the tie straps:

1.

Unload and mechanically install the UPS and IBCs, and if applicable IACs, according to the instructions in 
the applicable installation and operation manual.

2.

Remove the screws along each adjacent cabinet top panel securing the top panels (see Figure 1). Retain 
the hardware for later use.

3.

Install top tie strap between each UPS, IBC, IAC, and SIAC (see Figure 1). Secure the tie strap with 
retained hardware.

4.

If the long rear shipping bracket (tie strap) is installed between the UPS and an SIAC and no 
line-up-and-match IBC or IAC is installed, proceed to Step 7; otherwise, proceed to Step 5.

5.

Remove the screws along each adjacent cabinet (UPS, SIAC, IBC, or IAC) rear panel securing the cabinet 
rear panels (see Figure 1). Retain the hardware for later use.

6.

Install rear tie strap between each UPS, IBC, IAC, and SIAC (see Figure 1). Ensure strap is installed at the 
top of the cabinet. Secure the tie strap with retained hardware.

7.

Installation is complete.

For More Information

Refer to the applicable Eaton 93PM Installation and Operation manual for the following additional information:

l

Installation instructions, including site preparation, planning for installation, wiring and safety information, 
and detailed illustrations of cabinets with dimensional and connection point drawings

Visit www.eaton.com/powerquality or contact an Eaton service representative for information on how to obtain 
copies of these manuals.

Getting Help

If help is needed with any of these instructions, please call the 

Customer Reliability Center

 at:

United States:

1-800-843-9433

Canada:

1-800-461-9166 ext 260

All other countries: 

Call your local service representative

Please use the following e-mail address for comments, suggestions, or to report an error in these instructions:

E-ESSDocumentation@eaton.com

NOTE

Refer to the applicable installation and operation manual supplied with the UPS, 
SIAC, IBC, or IAC for dimensions and required clearances.

Seismic Tie Straps (part of Seismic Mounting Bracket Kit)

Top Tie Strap (Only provided with UPS kits. Strap is provided as standard with IACs. and IBCs)

1

Rear Tie Strap

1

Reviews: