Introduction
Eaton 93PM Integrated Battery Cabinet-Small Welded (IBC-SW) Installation Manual P-164000639—Rev 1
www.eaton.com/powerquality
1-3
1.2
Optional Thermal Sensor
Thermal runaway protection for VRLA batteries can be provided by installing an optional thermal sensor inside
the battery cabinet.
The sensor is wired to an UPS building alarm programmed to turn the charger off when a trip signal is received.
The thermal sensor will maintain the trip state until the temperature it is reset by service. Service should be
called to inspect the batteries and reset the sensor in case of such an event.
1.3
Model Configurations
The following model configurations are available:
l
93PM Integrated Battery Cabinet–Small Welded
- Line-up-and-match, top entry, or bottom entry standalone
- Top or rear exhaust ventilation
- Contains one battery string with either 36 batteries (432 Vdc version) or 40 batteries (480 Vdc version) to
be used with 93PM UPS systems
- Available Eaton PWHR12200W4FR or CSB HRL12200WFR batteries
- Up to four IBC–SWs can be paralleled with a 93PM 50 kW, 100 kW, 150 kW or 200 kW UPS to extend the
runtime
Note:
The Eaton IBC-SW 480 Vdc version is required when using the 480V Four Wire 93PM UPS systems.
1.4
Using This Manual
This manual describes how to install the IBC–SW and is divided into chapters. Read and understand the
procedures described to ensure trouble-free installation and operation.
Read through each procedure before beginning the procedure. Perform only those procedures that apply to the
UPS system being installed or operated.
Specifications listed in this manual are subject to change.
1.5
Conventions Used in This Manual
This manual uses these type conventions:
l
Bold type
highlights important concepts in discussions, key terms in procedures, and menu options, or
represents a command or option that you type or enter at a prompt.
l
Italic type highlights notes and new terms where they are defined.
l
Screen type
represents information that appears on the screen or LCD.
In this manual, the term UPS refers only to the UPS cabinet and its internal elements. The term UPS system
refers to the entire power protection system – the UPS cabinet, an external battery system, and options or
accessories installed.
The term line-up-and-match refers to accessory cabinets that are physically located adjacent to the UPS. The
term standalone refers to accessory cabinets that are located separate from the UPS.
Left and right side notations are referenced standing in front of the cabinet.
Icon
Description
Note
Information notes call attention to important features or instructions.
[Keys]
Brackets are used when referring to a specific key, such as [Enter] or [Ctrl].