Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04
3
11..22
O
Oppttiioonnaall TThheerrm
maall S
Seennssoorr
Thermal runaway protection for VRLA batteries can be provided by installing an optional thermal sensor inside
the battery cabinet.
The sensor is wired to an UPS building alarm programmed to turn the charger off when a trip signal is received.
The thermal sensor will maintain the trip state until the temperature it is reset by service. Service should be
called to inspect the batteries and reset the sensor in case of such an event.
11..33
M
Mooddeell C
Coonnffiigguurraattiioonnss
The following model configurations are available:
•
Eaton 93PM Universal Integrated Battery Cabinet-Large (432V and 480V)
–
Line-up-and-match, top or bottom entry standalone.
–
Contains one battery string to be used with Eaton 93PM UPS systems.
–
Available B37, E28, E39, E54, N54, or H41 batteries.
–
Up to four IBC-LWs can be paralleled to extend the run time. Use with a Eaton 93PM-L 20-120 kW
(208V) UPS. Use with a Eaton 93PM 20-50 kW UPS, Eaton 93PM 20-100 kW UPS, Eaton 93PM 20-
150 kW UPS, or Eaton 93PM 20-200 kW UPS.
–
Up to eight IBC-LWs can be paralleled to extend the run time. Use with a Eaton 93PM 100-400 kW
UPS.
•
Eaton 93PM Universal Integrated Battery Cabinet-Large High Rate (432V and 480V)
–
Line-up-and-match, top or bottom entry standalone.
–
Contains one battery string to be used with Eaton 93PM UPS systems.
–
Available B37, E54, N54 or H41 batteries.
–
Up to two IBC-LHWs can be paralleled to extend the run time. Use with a Eaton 93PM-L 20-120 kW
(208V) UPS. Use with a Eaton 93PM 20-50 kW UPS, Eaton 93PM 20-100 kW UPS, Eaton 93PM 20-
150 kW UPS, or Eaton 93PM 20-200 kW UPS.
–
Up to four IBC-LHWs can be paralleled to extend the run time. Use with a Eaton 93PM 100-400 kW
UPS.
NOTE
The Eaton IBC-LW or IBC-LHW 480 Vdc version is required when using the 480V Four
Wire 93PM UPS systems.
11..44
U
Ussiinngg TThhiiss M
Maannuuaall
This manual describes how to install the IBC and is divided into chapters. Read and understand the procedures
described to ensure trouble-free installation and operation.
Read through each procedure before beginning the procedure. Perform only those procedures that apply to the
UPS system being installed or operated.